TABLE 3.1 MAXIMUM SETPOINT TEMPERATURE FOR HWAT CONTROL MODE
HWAT-Y2
AMBIENT
208 V
240 V
277 V
60ºF
115ºF
120ºF
120ºF
70ºF
120ºF
125ºF
125ºF
80ºF
125ºF
125ºF
130ºF
90ºF
125ºF
130ºF
135ºF
HWAT-R2
AMBIENT
208 V
240 V
277 V
60ºF
135ºF
140ºF
140ºF
70ºF
140ºF
140ºF
145ºF
80ºF
145ºF
145ºF
150ºF
90ºF
145ºF
150ºF
150ºF
Default: HWAT-Y2: 115°F (46°C)
HWAT-R2: 125°F (52°C)
At this point the HWAT design wizard is complete and the HWAT circuit configuration window is
displayed.
3.2.2.
CONFIGURING HWAT
After completing the HWAT design wizard the Setup HWAT window appears where you can adjust
the input variables established in the design wizard and enter access additional menu windows.
Fig. 3.8 Setup|HWAT window
Economy Temperature (optional):
This value represents the temperature that you want the pipe to maintain when in economy mode.
This input is only accessible if the setpoint mode is set to Variable which applies the temperature
weekly setpoint 24/7 Scheduler function described in Appendix 5.2 24/7 Scheduler on page 127.
Enter the Economy temperature
Range
100°F (38°C) to less than the maintain temperature
Default
105°F (41°C)
Setpoint Mode:
Allows you to configure how the scheduling is done over a weekly timed calendar with 48 1/2-hour
program intervals per day available.
Содержание RAYCHEM ACS-30
Страница 1: ...nVent com 1 Raychem AR H58692 ACS30UIT2Programming EN 1805 PROGRAMMING GUIDE ACS 30 System...
Страница 2: ...nVent com 2 Raychem AR H58692 ACS30UIT2Programming EN 1805...
Страница 139: ...nVent com 139 Raychem AR H58692 ACS30UIT2Programming EN 1805 Fig 5 14 ACS 30 Program Integrator Printout...
Страница 144: ...nVent com 144 Raychem AR H58692 ACS30UIT2Programming EN 1805...