Input the Circuit Voltage
Voltage: 120, 208, 240 or 277 V (Standard ACS-PCM2-5 panels) Since the C910-485
measures voltage, this tab will not appear.
Default:
208 V
Assigning Power Cycle Test
The Setup|Maint. window allows you to enable the Power Cycle test start time and frequency. Once
the start time and test frequency are entered, the time of the next test will be displayed on this
screen.
Note:
If the circuit is disabled, forced on, or forced off, the power cycle test will be disabled until the
circuit is enabled.
Fig. 3.107
Setup|Maint. Window (Snow Melting Ambient Control)
Input the start time and frequency for the Power Cycle test:
Power Cycle Start Time:
The time of day to start the Power Cycle test
Range: 00:00–23:59
Default:
Each circuit is assigned a unique default start time calculated from the device
address and relay number.
Power Cycle Test Interval:
The frequency to run the Power Cycle test
Range:
Never, Daily, Weekly and Monthly
Default: Never