nVent.com
|
111
Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
ASSIGNING RTDS
After the control mode and parameters are set, tap Setup|RTDs window to assign RTDs to the
circuit.
Fig. 3.92
Setup|RTDs Window (Roof & Gutter - Surface Temp Control)
When in Surface temperature control mode you have the option of setting up to four inputs through
any RTD inputs in your system. For detailed information on the RTD window refer to section 2.2.3
Assigning and Sharing RTD Control and Monitoring on page 30
ASSIGNING GROUND-FAULT ALARM AND TRIP LEVEL
The G.F. window allows you to set the alarm and trip levels.
Fig. 3.93
Setup|G.F. Window (Roof & Gutter - Surface Temp Control)
Input the Ground-Fault Alarm and Ground-Fault Trip:
Ground-Fault Alarm:
When the ground-fault current exceeds this level the ACS-UIT2 goes into alarm.
Range:
10–200 mA
Default:
20 mA
Ground-Fault Trip:
When the ground-fault current exceeds this level the ACS-PCM2-5 turns off the
circuit relay.
Range:
10–200 mA
Default:
30 mA