nVent.com
|
77
Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
Default: Enable
Assigning Ground-Fault Alarm and Trip Levels
The Setup|G.F. window allows you to set the alarm and trip levels.
Fig. 3.42
Setup|G.F. window (Pipe Freeze PASC Control)
Input the Ground-Fault Alarm and Ground-Fault Trip:
Ground-Fault Alarm:
WHEN THE GROUND-FAULT CURRENT EXCEEDS THIS LEVEL THE
ACS-UIT2 GOES IN ALARM.
Range:
10–200 mA
Default:
20 mA
Ground-Fault Trip:
WHEN THE GROUND-FAULT CURRENT EXCEEDS THIS LEVEL THE
ACS-PCM2-5 TURNS OFF THE CIRCUIT RELAY.
Range:
10–200 mA
Default:
30 mA
Assigning Circuit Voltage
The Setup|Voltage window allows you to set the circuit voltage used to calculate the energy
consumption of the circuit.
Fig. 3.43
Setup|Voltage (Pipe Freeze PASC Control)