2.13. SYSTEM|RELAYS WINDOW
The System|Relays window lets you configure alarm relays.
Fig. 2.44
System|Relays window
There are three independent alarm relays in the ACS-UIT2 that can be used for remote annunciation
of alarms. Each relay can be programmed for a specific alarm type, multiple alarm types, or none. If
“Any Alarm” is chosen for a relay, any alarm condition will activate that relay.
2.14. SYSTEM|COMM WINDOW
The System|Comm window lets you set up communications with host systems.
Fig. 2.45
System|Comm window
The ACS-UIT2 can be connected to a Building Management System (BMS) or host computer using
an RS-485, RS-232, or 10/100Base-T Ethernet connection. All data and setup options are accessed
with communications that follow the Modbus (RTU/Modbus/TCP) protocol. To enable BMS
communications, please refer to the ACS-UIT2 Modbus Protocol document (H58685). ProtoNode
multi-protocol device servers are available through nVent. The ProtoNode is pre-programmed with
the Modbus mapping for ACS-30 and C910-485 controllers for BACnet, MetaSys and LonWorks
protocols.
IP Address/Subnet Mask
By default, the IP Address and Subnet Mask are automatically inserted. However, if the IP Address
or Subnet Mask needs to be changed, click on the IP Address or Subnet window and then on the
LAN91C1111 icon.
Содержание RAYCHEM ACS-30
Страница 1: ...nVent com 1 Raychem AR H58692 ACS30UIT2Programming EN 1805 PROGRAMMING GUIDE ACS 30 System...
Страница 2: ...nVent com 2 Raychem AR H58692 ACS30UIT2Programming EN 1805...
Страница 139: ...nVent com 139 Raychem AR H58692 ACS30UIT2Programming EN 1805 Fig 5 14 ACS 30 Program Integrator Printout...
Страница 144: ...nVent com 144 Raychem AR H58692 ACS30UIT2Programming EN 1805...