Chapter 1 - Getting Started
Optional DC Hot Swappable Power Supplies
6
If the power supply cooling fan fails, the Fault LED will illuminate and the alarm
will sound.
The power supply also has an amber general Fault LED. If you have a dual power
supply configuration and power is not applied to one of the power supplies, the
general Fault LED is illuminated.
CAUTION:
The DC system must be installed in a restricted access location, in
accordance with the intent of the National Electrical Code. A
restricted access location is defined as an area intended only for
qualified or trained personnel only. Access should be controlled by
key lock or access card.
Each power supply has a special cable connector that plugs into the face of the
power supply and mechanically connects to a DC feed system. Refer to the
Installation chapter for cabling procedures.
DC Source Site Requirements
The power feed must be electrically isolated from any AC power source, provide
a reliable connection to earth (battery room positive bus is connected to the
grounding electrode), and capable of providing up to 600 watts of continuous
power per feed pair.
Over-current Protection Requirements
Over-current protection devices must be provided as part of each equipment
rack. Circuit breakers must be located between the DC power feed source and
the power supplies (two 20 amp double-pole fast trip DC-rated circuit breakers
for each power supply).
NOTE:
Over-current protection devices must meet applicable national and local
electrical safety codes and be approved for the intended application.
Electrical Equipment
Requirement
Voltage
-36 to -72 VDC
Max. Operating Current
13.5 amp to 6.3 amps
Max. Input Surge Current
20.25 amps
4700S.book Page 6 Wednesday, April 6, 2005 2:14 PM
Содержание NexStor 4700S Series
Страница 2: ...4700S book Page 2 Wednesday April 6 2005 2 14 PM...
Страница 8: ...Table of Contents iv 4700S book Page iv Wednesday April 6 2005 2 14 PM...
Страница 74: ...Chapter 5 Troubleshooting Host SCSI Channel Problems 62 4700S book Page 62 Wednesday April 6 2005 2 14 PM...
Страница 90: ...Chapter 6 Maintenance Replacing the Enclosure 78 4700S book Page 78 Wednesday April 6 2005 2 14 PM...
Страница 94: ...Appendix A Technical Information Specifications 82 4700S book Page 82 Wednesday April 6 2005 2 14 PM...
Страница 108: ...Index 96 4700S book Page 96 Wednesday April 6 2005 2 14 PM...
Страница 109: ...4700S book Page 97 Wednesday April 6 2005 2 14 PM...