7 Settings
PCS-9611 Feeder Relay
7-13
Date: 2014-04-08
13
50/51SEF3.3I0_Set
The current setting of the stage 3 sensitive earth
fault protection
0.005~1.0A
0.001A
14
50/51SEF3.t_Op
The time setting of the stage 3 sensitive earth
fault protection
0~100s
0.001s
15
50/51SEF3.Opt_Dir
The setting is used to select the directional mode
for the stage 3 SEF protection, see
Section 3.6.3
0~2
1
16
50/51SEF3.En
The logic setting of the stage 3 sensitive earth
fault protection
0~1
1
17
50/51SEF3.OutMap
The output matrix setting of the stage 3 sensitive
earth fault protection
0x00000 ~
0xFFFFF
1
18
50/51SEF4.3I0_Set
The current setting of the stage 4 sensitive earth
fault protection
0.005~1.0A
0.001A
19
50/51SEF4.t_Op
The time setting of the stage 4 sensitive earth
fault protection
0~100s
0.001s
20
50/51SEF4.Opt_Dir
The setting is used to select the directional mode
for the stage 4 SEF protection, see
Section 3.6.3
0~2
1
21
50/51SEF4.En
The logic setting of the stage 4 sensitive earth
fault protection
0~1
1
22
50/51SEF4.OutMap
The output matrix setting of the stage 4 sensitive
earth fault protection
0x00000 ~
0xFFFFF
1
23
50/51SEF4.Opt_Curve
The setting is for selecting the inverse time
characteristic curve for SEF4 protection
0~13
1
24
50/51SEF4.TMS
The time multiplier setting of the IDMT sensitive
earth fault protection
0.05~100.0
0.001
25
50/51SEF4.tmin
The minimum operation time setting of the IDMT
sensitive earth fault protection
0~100s
0.001s
26
50/51SEF4.K
Constant
“k” for the IDMT sensitive earth fault
protection, see
Section 3.6.2
0.001~120.0
0.0001
27
50/51SEF4.C
Constant
“C” for the IDMT sensitive earth fault
protection, see
Section 3.6.2
0.00~1.00
0.0001
28
50/51SEF4.Alpha
Constant
“α” for the IDMT sensitive earth fault
protection, see
Section 3.6.2
0.01~3.00
0.0001
NOTE!
1. The setting [50/51SEFx.Opt_Dir] (x: 1~4) is used to select the directional mode for the stage
x (x: 1~4) sensitive earth fault protection respectively.
“0” is the non-directional mode; “1” is
the forward directional mode; and
“2” is the reverse directional mode.
7.3.5 Breaker Failure Protection Settings
The breaker failure protection settings (in the submenu
“
BFP Settings
”) are used to determine the
characteristic of the breaker failure protection.
All the settings of the breaker failure protection are listed in the following table.
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...