7 Settings
PCS-9611 Feeder Relay
7-11
Date: 2014-04-08
35
A.50/51G4.Opt_Curve
The setting is for selecting the inverse time
characteristic curve for the No.2 ROC4 protection
0~13
1
36
A.50/51G4.TMS
The time multiplier setting of the No.2 stage 4
zero sequence IDMT overcurrent protection
0.05~100.0
0.001
37
A.50/51G4.tmin
The minimum operation time setting of the No.2
stage 4 zero sequence IDMT o vercurrent
protection
0~100s
0.001s
38
A.50/51G4.K
Constant
“k” for the No.2 stage 4 zero sequence
IDMT o vercurrent protection, see
Section 3.5.2
0.001~120.0
0.0001
39
A.50/51G4.C
Constant
“C” for the No.2 stage 4 zero sequence
IDMT o vercurrent protection, see
Section 3.5.2
0.00~1.00
0.0001
40
A.50/51G4.Alpha
Constant
“α” for the No.2 stage 4 zero sequence
IDMT o vercurrent protection, see
Section 3.5.2
0.01~3.00
0.0001
NOTE!
1. The setting [A.50/51Gx.Opt_Dir] (x: 1~4) is used to select the directional mode for the No.2
stage x (x: 1~4) zero sequence overcurrent protection respectively.
“0” is the non-directional
mode;
“1” is the forward directional mode; and “2” is the reverse directional mode.
7.3.3 Negative Sequence Overcurrent Protection Settings
The negative sequence overcurrent protection settings (in the submenu
“
NegOC Settings
”) are
used to determine the characteristic of the negative sequence overcurrent protection.
All the settings of the negative sequence overcurrent protection are listed in the following table.
No.
Menu text
Explanation
Range
Step
1
50/51Q1.I2_Set
The current s etting of the stage 1 negative
sequence overcurrent protection
0.05In~4In
0.001A
2
50/51Q1.t_Op
The time s etting of the stage 1 negative sequence
overcurrent protection
0.03~100s
0.001s
3
50/51Q1.En
The logic setting of the stage 1 negative sequence
overcurrent protection
0~1
1
4
50/51Q1.OutMap
The output matrix setting of the stage 1 negative
sequence overcurrent protection
0x00000 ~
0xFFFFF
1
5
50/51Q2.I2_Set
The current s etting of the stage 2 negative
sequence overcurrent protection
0.05In~4In
0.001A
6
50/51Q2.t_Op
The time s etting of the stage 2 negative sequence
overcurrent protection
0.03~100s
0.001s
7
50/51Q2.En
The logic setting of the stage 2 negative sequence
overcurrent protection
0~1
1
8
50/51Q2.OutMap
The output matrix setting of the stage 2 negative
sequence overcurrent protection
0x00000 ~
0xFFFFF
1
9
50/51Q2.Opt_Curve
The setting is for selecting the inverse time
characteristic curve for the NOC2 protection
0~13
1
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...