3 Operation Theory
PCS-9611 Feeder Relay
3-47
Date: 2014-04-08
3.14 Zero Sequence Overvoltage Protection
3.14.1 Zero Sequence Overvoltage Protection Theory
On a healthy three-phase power system, the addition of each of the three-phase to earth voltages
is nominally zero. However, when an earth fault occurs on the primary system, the balance is
upset and a residual voltage is produced. Hence, a zero sequence overvoltage protection can be
used to offer earth fault protection on such a system.
The residual voltage could be measured at the secondary terminals of a voltage transformer
having a “broken delta” secondary connection, or it can be calculated from the three phase
voltages; which is decided by the setting [Opt_3U0].
This relay provides a two-stage zero sequence overvoltage protection with definite time delay
characteristics. The two stages have same protection logics.
The following figure shows the logic diagram of the stage 1 zero sequence overvoltage protection.
[59G1.En1]
[59G1.En]
U
0
> [59G1.3U0_Set]
&
[59G1.Op]
[59G1.St]
[59G1.Blk]
t
ROV1
0
Figure 3.14-1 Logic diagram of the stage 1 ROV protection
Where:
[59G1.3U0_Set] is the voltage setting of the stage 1 zero sequence overvoltage protection;
“t
ROV1
” is the setting [59G1.t_Op], the time setting of the stage 1 zero sequence overvoltage
protection;
[59G1.En] is logic setting of the stage 1 zero sequence overvoltage protectio n.
[59G1.En1] is the binary signal for enabling the stage 1 zero sequence overvoltage
protection;
[59G1.Blk] is the binary signal for blocking the stage 1 zero sequence overvoltage protection.
3.14.2 Zero Sequence Overvoltage Protection Settings
All the settings of the zero sequence overvoltage protection are listed in the following table. For
the information about the common explanation of the settings, see
Section 7.3
.
No.
Menu text
Explanation
Range
Step
1
59G1.3U0_Set
The voltage setting of the stage 1 zero sequence
overvoltage protection
2~160V
0.001V
2
59G1.t_Op
The time s etting of the stage 1 zero sequence
overvoltage protection
0~100s
0.001s
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...