7 Settings
PCS-9611 Feeder Relay
7-17
Date: 2014-04-08
when the enabling conditions are satisfied (See
Section 3.10
).
2. The setting [SOTF.Opt_Mode] is used for selecting the acceleration tripping mode of the
SOTF protection. Setting as
“1” means accelerated tripping before auto-reclosing; and setting
as
“0” means accelerated tripping after auto-reclosing.
7.3.9 Thermal Overload Protection Settings
The thermal overload protection settings (in submenu
“
ThOvLd Settings
”) are used to determine
the characteristic of the thermal overload protection.
All the settings of the thermal overload protection are listed in the following table.
No.
Menu text
Explanation
Range
Step
1
49.Ib_Set
The reference current s etting of the thermal
overload protection
0.05In~3.0In
0.001A
2
49.Tau
The time constant s etting of the IDMT o verload
protection
10~6000s
0.001s
1
49.C_Disspt
The thermal dissipation constant s etting of the
thermal overload protection
0.2~5.0
0.001
3
49.K_Trp
The factor setting of the thermal overload
protection which is associated to the thermal state
formula
1.0~3.0
0.001
4
49.K_Alm
The factor setting of the thermal overload alarm
element which is associated to the thermal state
formula
1.0~3.0
0.001
5
49.En_Trp
The logic s etting of the thermal overload
protection for tripping
0~1
1
6
49.En_Alm
The logic s etting of the thermal overload
protection for alarming
0~1
1
7
49.OutMap
The output matrix setting of the thermal overload
protection
0x00000 ~
0xFFFFF
1
7.3.10 Overvoltage and Undervoltage Protection Settings
The overvoltage and undervoltage protection settings (in the submenu
“
VoltProt Settings
”) are
used to determine the characteristic of the overvoltage and undervoltage protections.
All the settings of the overvoltage and undervoltage protections are listed in the following table.
No.
Menu text
Explanation
Range
Step
1
27P.Opt_1P/3P
The setting for s electing the undervoltage
protection calculation method
0~1
1
2
27P.Opt_Up/Upp
The setting for selecting the voltage input mode
for the undervoltage protection
0~1
1
3
27P1.U_Set
The voltage setting of the stage 1 undervoltage
protection
2~120V
0.001V
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...