12 Commissioning
PCS-9611 Feeder Relay
12-13
Date: 2014-04-08
2. De-energize all the binary inputs of this relay.
3. Simulate a normal condition with normal protection voltages and the circuit breaker is closed.
4. Simulate an undervoltage condition; anyone of the three phase-to-phase voltages is less than
0.95 × [27P1.U_Set].
5. After the period of [27P1.t_Op], the stage 1 undervoltage protection will operate and issue the
trip command. The “
TRIP
” LED indicator will be on; a relevant report will be shown on the
LCD.
6. After the fault is disappeared, this relay will restore the stage 1 undervoltage protection
automatically. Restore the “
TRIP
” indicator and the LCD manually.
12.5.3.10 Overvoltage Protection Check
This check, performed the stage 1 overvoltage protection function in the No.1 setting group,
demonstrates that the relay is operating correctly at the application-specific settings.
1. Enable the stage 1 overvoltage protection.
Set the logic setting [59P1.En
] as “1” in the submenu “
VoltProt Settings
”.
Set the setting [59P.Opt_1P/3P
] as “1” in the submenu “
VoltProt Settings
”.
Set the setting [59P.Opt_Up/Upp
] as “1” in the submenu “
VoltProt Settings
”.
Set the setting [59P.OutMap
] as “0x0001” in the submenu “
VoltProt Settings
”.
Set other logic settings as “0” in the submenu “
VoltProt Settings
”.
2. De-energize all the binary inputs of this relay.
3. Simulate a normal condition with normal protection voltages.
4. Simulate an overvoltage condition; anyone of the three phase-to-phase voltages is greater
than 1.05 × [59P1.U_Set].
5. After the period of [59P1.t_Op], the stage 1 overvoltage protection will operate and issue the
trip command. The “
TRIP
” LED indicator will be on; a relevant report will be shown on the
LCD.
6. After the fault is disappeared, this relay will restore the stage 1 overvoltage protection
automatically. Restore the “
TRIP
” indicator and the LCD manually.
12.5.3.11 Negative Sequence Overvoltage Protection Check
This check, performed the negative sequence overvoltage protection function in the No.1 setting
group, demonstrates that the relay is operating correctly at the application -specific settings.
1. Enable the negative sequence overvoltage protection.
Set the logic setting [59Q.En
] as “1” in the submenu “
NegOV Settings
”.
Set the setting [59Q.OutMap
] as “0x0001” in the submenu “
NegOV Settings
”.
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...