![NR Electric PCS-9611 Скачать руководство пользователя страница 153](http://html1.mh-extra.com/html/nr-electric/pcs-9611/pcs-9611_instruction-manual_1713962153.webp)
7 Settings
PCS-9611 Feeder Relay
7-9
Date: 2014-04-08
43
50/51G5.En
The logic setting of the No.1 stage 5 zero
sequence overcurrent protection
0~1
1
44
50/51G6.3I0_Set
The current s etting of the No.1 stage 6 zero
sequence overcurrent protection
0.05In~30In
0.001A
45
50/51G6.t_Op
The time s etting of the No.1 stage 6 zero
sequence overcurrent protection
0~100s
0.001s
46
50/51G6.En
The logic setting of the No.1 stage 6 zero
sequence overcurrent protection
0~1
1
NOTE!
1. The setting [50/51Gx.Opt_Dir] (x: 1~4) is used to select the directional mode for the No.1
stage x (x: 1~4) zero sequence overcurrent protection respectively.
“0” is the non-directional
mode;
“1” is the forward directional mode; and “2” is the reverse directional mode.
All the settings of the No.2 zero sequence overcurrent protection are listed in the following table.
No.
Menu text
Explanation
Range
Step
1
A.50/51G.RCA
The relay characteristic angle for the No.2
directional zero sequence overcurrent protection
-180°~179°
1°
2
A.50/51G.En_VTS_Blk
The logic setting of the function which blocks the
2ROC protection related voltage measurement
when the voltage transformer is failed
0~1
1
3
A.50/51G.K_Hm2
The percent setting of the harmonic blocking
element for the No.2 ROC protection
0.05~1.00
0.001
4
A.50/51G.3I0_Rls_HmBlk
The current setting for releasing the harmonic
blocking element of the No.2 ROC protection
0.05In~30In
0.001A
5
A.50/51G1.3I0_Set
The current s etting of the No.2 stage 1 zero
sequence overcurrent protection
0.05In~30In
0.001A
6
A.50/51G1.t_Op
The time s etting of the No.2 stage 1 zero
sequence overcurrent protection
0~100s
0.001s
7
A.50/51G1.Opt_Dir
The setting is used to select the directional mode
for the No.2 ROC1 protection
0~2
1
8
A.50/51G1.En_Hm_Blk
The logic setting of the harmonic blocking element
for the No.2 ROC1 protection
0~1
1
9
A.50/51G1.En
The logic setting of the No.2 stage 1 zero
sequence overcurrent protection
0~1
1
10
A.50/51G1.OutMap
The output matrix setting of the No.2 stage 1 zero
sequence overcurrent protection
0x00000 ~
0xFFFFF
1
11
A.50/51G2.3I0_Set
The current s etting of the No.2 stage 2 zero
sequence overcurrent protection
0.05In~30In
0.001A
12
A.50/51G2.t_Op
The time s etting of the No.2 stage 2 zero
sequence overcurrent protection
0~100s
0.001s
13
A.50/51G2.Opt_Dir
The setting is used to select the directional mode
for the No.2 ROC2 protection
0~2
1
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...