7 Settings
PCS-9611 Feeder Relay
7-22
Date: 2014-04-08
41
81R2.t_Op
The time setting of the stage 2 frequency
rate-of-change protection
0~100s
0.001s
42
81R2.En
The logic setting of the stage 2 frequency
rate-of-change protection
0~1
1
43
81R2.OutMap
The output matrix setting of the stage 2 frequency
rate-of-change protection
0x00000 ~
0xFFFFF
1
44
81R3.df/dt_Set
The
setting
of
the
stage
3
frequency
rate-of-change protection
-10~10Hz/s
0.001
Hz/s
45
81R3.f_Pkp
The pickup frequency setting of the stage 3
frequency rate-of-change protection
45~65Hz
0.001Hz
46
81R3.t_Op
The time setting of the stage 3 frequency
rate-of-change protection
0~100s
0.001s
47
81R3.En
The logic setting of the stage 3 frequency
rate-of-change protection
0~1
1
48
81R3.OutMap
The output matrix setting of the stage 3 frequency
rate-of-change protection
0x00000 ~
0xFFFFF
1
49
81R4.df/dt_Set
The
setting
of
the
stage
4
frequency
rate-of-change protection
-10~10Hz/s
0.001
Hz/s
50
81R4.f_Pkp
The pickup frequency setting of the stage 4
frequency rate-of-change protection
45~65Hz
0.001Hz
51
81R4.t_Op
The time setting of the stage 4 frequency
rate-of-change protection
0~100s
0.001s
52
81R4.En
The logic setting of the stage 4 frequency
rate-of-change protection
0~1
1
53
81R4.OutMap
The output matrix setting of the stage 4 frequency
rate-of-change protection
0x00000 ~
0xFFFFF
1
7.3.14 Auto-recloser Settings
The auto-recloser settings (in submenu
“
AR Settings
”) are used to determine the characteristic of
the auto-recloser.
All the settings of the auto-recloser are listed in the following table.
No.
Menu text
Explanation
Range
Step
1
79.t_CBClsd
The time setting of the minimum time delay for
ensuring the CB is closed
0.01~600s
0.001s
2
79.t_DDO_BlkAR
The time pulse width for ensuring the AR blocking
signal
0.01~600s
0.001s
3
79.t_CBReady
The time setting of the time delay for ensuring the
CB is ready
0.01~600s
0.001s
4
79.t_Fail
The time setting of the time delay for checking the
CB position
0.01~600s
0.001s
5
79.t_3PS1
The time setting of the 1
st
shot auto-recloser
0~600s
0.001s
6
79.t_3PS2
The time setting of the 2
nd
shot auto-recloser
0~600s
0.001s
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...