3 Operation Theory
PCS-9611 Feeder Relay
3-25
Date: 2014-04-08
18
50/51G3.t_Op
The time s etting of the No.1 stage 3 zero
sequence overcurrent protection
0~100s
0.001s
19
50/51G3.Opt_Dir
The setting is used to select the directional mode
for the No.1 ROC3 protection, see
Section 3.5.3
0~2
1
20
50/51G3.En_Hm_Blk
The logic setting of the harmonic blocking element
for the No.1 ROC3 protection
0~1
1
21
50/51G3.En
The logic setting of the No.1 stage 3 zero
sequence overcurrent protection
0~1
1
22
50/51G3.OutMap
The output matrix setting of the No.1 stage 3 zero
sequence overcurrent protection
0x00000 ~
0xFFFFF
1
23
50/51G3.Opt_Curve
The setting is for selecting the inverse time
characteristic curve for the No.1 ROC3 protection
0~13
1
24
50/51G3.TMS
The time multiplier setting of the No.1 stage 3
zero sequence IDMT overcurrent protection
0.05~100.0
0.001
25
50/51G3.tmin
The minimum operation time setting of the No.1
stage 3 zero sequence IDMT o vercurrent
protection
0~100s
0.001s
26
50/51G3.K
Constant
“k” for the No.1 stage 3 zero sequence
IDMT o vercurrent protection, see
Section 3.5.2
0.001~120.0
0.0001
27
50/51G3.C
Constant
“C” for the No.1 stage 3 zero sequence
IDMT o vercurrent protection, see
Section 3.5.2
0.00~1.00
0.0001
28
50/51G3.Alpha
Constant
“α” for the No.1 stage 3 zero sequence
IDMT o vercurrent protection, see
Section 3.5.2
0.01~3.00
0.0001
29
50/51G4.3I0_Set
The current setting of the No.1 stage 4 zero
sequence overcurrent protection
0.05In~30In
0.001A
30
50/51G4.t_Op
The time s etting of the No.1 stage 4 zero
sequence overcurrent protection
0~100s
0.001s
31
50/51G4.Opt_Dir
The setting is used to select the directional mode
for the No.1 ROC4 protection, see
Section 3.5.3
0~2
1
32
50/51G4.En_Hm_Blk
The logic setting of the harmonic blocking element
for the No.1 ROC4 protection
0~1
1
33
50/51G4.En
The logic setting of the No.1 stage 4 zero
sequence overcurrent protection
0~1
1
34
50/51G4.OutMap
The output matrix setting of the No.1 stage 4 zero
sequence overcurrent protection
0x00000 ~
0xFFFFF
1
35
50/51G4.Opt_Curve
The setting is for selecting the inverse time
characteristic curve for the No.1 ROC4 protection
0~13
1
36
50/51G4.TMS
The time multiplier setting of the No.1 stage 4
zero sequence IDMT overcurrent protection
0.05~100.0
0.001
37
50/51G4.tmin
The minimum operation time setting of the No.1
stage 4 zero sequence IDMT o vercurrent
protection
0~100s
0.001s
38
50/51G4.K
Constant
“k” for the No.1 stage 4 zero sequence
IDMT o vercurrent protection, see
Section 3.5.2
0.001~120.0
0.0001
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...