![NR Electric PCS-9611 Скачать руководство пользователя страница 96](http://html1.mh-extra.com/html/nr-electric/pcs-9611/pcs-9611_instruction-manual_1713962096.webp)
3 Operation Theory
PCS-9611 Feeder Relay
3-60
Date: 2014-04-08
“U
Sy n
” is the synchro-check voltage;
“ΔU” is the voltage difference of the protection voltage and the synchro-check voltage;
“Δf” is the frequency difference of the protection voltage and the synchro-check voltage;
“Δδ” is the angle difference of the protection voltage and the synchro-check voltage;
[25.U_Lv] is the voltage setting of the live voltage;
[25A.U_Diff] is the voltage difference setting of the synchronism check function for the
auto-recloser;
[25A.f_Diff] is the frequency difference setting of the synchronism check function for the
auto-recloser;
[25A.phi_Diff] is the phase angle difference setting of the synchronism check function for
the auto-recloser;
“t
ARSy nChk
” is the setting [25A.t_SynChk], the time setting of the synchronism check
function for the auto-recloser.
Dead check mode
In dead check mode case, the relay checks the protection voltage and synchro-check voltage.
There are several kinds of dead check modes which are supported in this relay and the dead
check mode can be selected according to the demands of a practical engineering by the
setting [25A.Opt_DdChk].
The relationship between the setting [25A.Opt_DdChk] and the dead check mode is listed in
following table.
[25A.Opt_DdChk]
Description of Dead Check Mode
1
The protection voltage is dead, and the synchro-check voltage is dead.
2
The protection voltage is dead, and the synchro-check voltage is live.
3
The protection voltage is live, and the synchro-check voltage is dead.
4
The protection voltage is dead, the synchro-check voltage is live or dead.
5
The synchro-check voltage is dead, the protection voltage is live or dead.
6
One of the two voltages is live, another one is dead.
7
One of the two voltages is dead, another one is live or dead.
The logic diagram of the dead check element for the auto-recloser is shown as below.
25A.Ok_DdChk
Dead
Check
U
Prot
< [25.U_Dd]
U
Syn
< [25.U_Dd]/[25.U_Comp]
U
Prot
> [25.U_Dd]
U
Syn
> [25.U_Dd]/[25.U_Comp]
[25A.Opt_DdChk]
&
[VTS.Alm]
[VTS.Alm_SynVT]
t
ARDdChk
0
Figure 3.17-6 Logic diagram of the dead check element for AR
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...