8 Human Machine Interface
PCS-9611 Feeder Relay
8-30
Date: 2014-04-08
8.3 Understand the LCD Display
8.3.1 Display When Tripping
If there is any protection element operating, a brief tripping report will appear on the LCD, and the
backlight of the LCD and the LED “
TRIP
” will be on simultaneously.
The format of the fault report is shown as below.
Trip NO.4
fmax 50.030Hz
3I0_Calmax 01.011A
Ipmax 03.040A
0105ms 50/51P1.Op
0000ms FD.Pkp
2011-02-08 11:18:18:988ms
fmin 49.990Hz
Figure 8.3-1 LCD display of trip report
The first line shows the report title and the sequence number of the history trip report, and the
second line shows the operation time of the history trip report. Other lines show the protection
elements and fault information one by one according to the relative time sequence. The fault
information includes fault phase, maximum fault value and minimum fault value.
NOTE!
In case more than one protection element has operated, the relevant report will
be displayed alternatively one by one according to time sequence on the LCD. And the
fault information is listed after all the protection elements.
The trip report will keep being displayed on LCD until an acknowledgement is received by pressing
the key “
ENT
”+“
ESC
”, by energizing the binary input [BI_RstTarg] or by executing the submenu
“
Reset Target
”. The default display then appears on LCD and LED “
TRIP
” is turned off.
Protection elements listed below may be displayed.
No.
Protection Element
Description
1
FD.Pkp
The fault detector operates.
2
Op_Prot
Anyone of the protective elements in this relay operates.
3
50/51P1.St
The s tage 1 overcurrent protection picks up.
4
50/51P1.Op
The s tage 1 overcurrent protection operates.
5
50/51P2.St
The s tage 2 overcurrent protection picks up.
6
50/51P2.Op
The s tage 2 overcurrent protection operates.
7
50/51P3.St
The s tage 3 overcurrent protection picks up.
8
50/51P3.Op
The s tage 3 overcurrent protection operates.
9
50/51P4.St
The stage 4 overcurrent protection picks up.
10
50/51P4.Op
The stage 4 overcurrent protection operates.
11
50/51P5.St
The stage 5 overcurrent protection picks up.
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...