5 Parameter
BU 0250 en-3021
89
Information
Torque limitation during active setpoint delay
(P107 / P114)
During an active setpoint delay, the torque is limited to a maximum of 160% of the rated
torque. This prevents the occurrence of excessive currents in the inverter or breakdown of the
motor if
•
For application of the brake, the
brake reaction time
(P107) is set too long.
•
For release of the brake, the value for the
absolute minimum frequency
(P505) is set too
high.
Pos: 256 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P100-P199/Parameter P107 – Einfallzeit Bremse_Beispiel @ 4\mod_1396519433556_388.docx @ 123851 @ @ 1
Recommendation for applications:
Lifting equipment with brake, without speed feedback Lifting equipment with brake
P114 = 0.02...0.4 s *
P107 = 0.02...0.4 s *
P201…P208 = Motor data
P434 = 1 (ext. brake)
P505 = 2...4 Hz
for safe start-up
P112 = 401 (off)
P536 = 2.1 (off)
P537 = 150 %
P539 = 2/3 (I
SD
monitoring)
to prevent load drops
P214 = 50...100 % (precontrol)
* Settings (P107/114) depending on
brake type and motor size. At low power
levels (< 1.5 kW) lower values apply for
higher power ratings (> 4.0 kW) are
larger values.
Output
frequency
P107
Brake released
P114
or
P107, when P114 = 0
ON signal
P505
OFF signal
Time
Pos: 257 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P100-P199/Parameter P108 – Ausschaltmodus @ 0\mod_1327575421965_388.docx @ 7665 @ @ 1