5 Parameter
BU 0250 en-3021
123
Value
Function
Description
Signal
5
The operating parameter set is selected via correspondingly
parametrised digital inputs or BUS control. Switch-over may
be performed during operation (online). Coding is binary
according to the following pattern.
If enabling is via the keyboard (SimpleBox or ParameterBox),
the operating parameter set corresponds to the setting in
P100.
Setting
Digital input
function [8]
Digital input
function [17]
0 =
Parameter set 1
LOW
LOW
1 =
Parameter set 2
HIGH
LOW
2 =
Parameter set 3
LOW
HIGH
3 =
Parameter set 4
HIGH
HIGH
Pos: 383 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P425 – Kaltleitereingang [SK 2xxE-FDS] @ 12\mod_1467281315705_388.docx @ 335200 @ @ 1
P425
Thermistor input
(Function thermistor input)
S
0 ... 1
{ 1 }
A connected thermistor is evaluated by the device This function must be disabled if no thermistor
is connected. Otherwise the device will enter a fault state with an overtemperature message
(E2.0).
0 = Off:
Thermistor input not monitored
1 = On:
Thermistor input monitoring active
Note:
If monitoring is deactivated, the device no longer provides direct overtemperature protection
for the motor.
Pos: 384 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P426 – Schnellhaltezeit [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_1347348745067_388.docx @ 44464 @ @ 1
P426
Quick stop time
(Quick stop time)
S
P
0 ... 320.00 sec
{ 0.10 }
Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
Pos: 385 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P427 – Schnellhalt bei Störung [SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346931805833_388.docx @ 42720 @ @ 1
P427
Quick stop on error
(Quick
stop on error)
S
0 ... 2
{ 0 }
Activation of automatic emergency stop following error
0 =
Disabled:
Automatic emergency stop following error is deactivated
1 =
Reserved
2 =
Activated:
Automatic emergency stop following fault
A quick stop can be triggered by error
E2.x, E7.0, E10.x, E12.8, E12.9
and
E19.0
.
Pos: 386 /Allgemein/Allgemeingültige Module/---------Seitenumbruch kompakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1