NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) – Users Manual for Frequency Inverters as Field Distributors
178
BU 0250 en-3021
Pos: 630 /Anleitungen/Elektronik/FU und Starter/7. Technische Daten/Elektrische Daten_Einleitung [SK xxxE-FDS] @ 12\mod_1467362340032_388.docx @ 335899 @ 2 @ 1
7.3 Electrical data
The following tables contain the data which is relevant for UL.
Details of the UL/CSA approval conditions can be found in Section 1.6.1 "UL and CSA approval". Use
of mains fuses which are faster than those stated is permissible.
Pos: 631 /Anleitungen/Elektronik/FU und Starter/7. Technische Daten/Elektrische Daten [SK 1xxE, SK 2xxE, SK xxxE-FDS]/Elektrische Daten 3~ 400V [SK 2xxE-FDS] @ 50\mod_1600933499782_388.docx @ 2672841 @ 3 @ 1
7.3.1 Electrical data 3~400 V
Device type
SK 2xxE
-
FDS
-
…
-370-340-
-550-340-
-750-340-
-111-340-
-151-340-
Size
0
0
0
1
1
Nominal motor power
(4-pole standard motor)
400 V
0.37 kW
0.55 kW
0.75 kW
1.1 kW
1.5 kW
480 V
½ hp
¾ hp
1 hp
1½ hp
2 hp
Mains voltage
400 V
3 AC
380 … 500 V, - 20 % / + 10 %, 47 … 63 Hz
Input current
rms
1)
1.1 A
1.7 A
2.2 A
2.9 A
3.8 A
FLA
2)
1.0 A
1.6 A
2.0 A
2.7 A
3.4 A
Output voltage
400 V
3 AC
0 … Mains voltage
Output current
rms
1)
1.3 A
1.7 A
2.3 A
3.1 A
4.0 A
FLA
2)
1.2 A
1.5 A
2.1 A
2.8 A
3.6 A
Min. brake resistance
Accessories
320
Ω
200
Ω
200
Ω
200
Ω
200
Ω
Max. continuous power / max. continuous current
S1-40°C 0.37kW / 1.3A
0.55kW / 1.7A
0.75kW / 2.3A
1.1kW / 3.1A
1.5kW / 4.0A
General fuses (AC) (recommended)
slow-blowing
10 A
4)
10 A
4)
10 A
4)
10 A
4)
10 A
4)
Isc
5)
[A]
UL fuses (AC) – permitted
Class
20 00
0
65 00
0
F
us
e
CC, J, R, T, G, RK1, RK5
X
30 A
30 A
30 A
30 A
30 A
CB
6)
480 V
X
30 A
30 A
30 A
30 A
30 A
500 V
X
30 A
30 A
30 A
30 A
30 A
1) Note the derating curve (
Section 8.4.4 "Reduced output current due to low voltage").
2) FLA – Full Load Current, maximum current for the entire mains voltage range as stated above (380 V – 500 V) according to UL/CSA
3) Only with "Fan" (standard equipment)
4) for group fuses: maximum fuse size: 30 A
5) Maximum mains short-circuit current, Note: Further restrictions are possible depending on the plug connector which is used (