4.5.1 The bus system
General information
The
A
ctuator
S
ensor
I
nterface (AS-Interface) is a bus system for the lower field bus level. It has been
defined in the AS-Interface
Complete Specification
and standardised according to EN 50295,
IEC62026.
The transfer principle is a single-master system with cyclic polling. Since the
Complete Specification
V2.1
, a maximum of
31 standard slaves
using the device profile
S-7.0.
, or
62 slaves in the
extended addressing mode
using the device profile
S-7.A.
could have been operated with any
network structure at an unshielded two-wire line up to 100 m long.
Doubling the number of possible slave participants is realised by the double assignment of the
addresses 1-31 and the “A slave” or “B slave” labelling. Slaves in the extended addressing mode are
labelled by the ID code A and can be clearly identified by the master.
Devices with slave profiles
S-7.0
and
S-7.A.
can be operated together within an AS-i network with
version 2.1 and higher (
master profile M4
), considering the address assignment (see example).
Permissible
Not permissible
Standard slave 1 (address 6)
Standard slave 1 (address 6)
A/B slave 1 (address 7A)
Standard slave 2 (address 7)
A/B slave 2 (address 7B)
A/B slave 1 (address 7B)
Standard slave 2 (address 8)
Standard slave 3 (address 8)
Addressing is done via the master that also provides further management functions, or via a separate
addressing unit.
Pos: 183 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/AS-Interface [alle Geräte]/Das Bussystem_02 [SK 1xxE, SK 2xxE, SK xxxE-FDS] @ 41\mod_1583913774679_388.docx @ 2596538 @ 5 @ 1
Device-specific information
The transfer of the 4-bit application data (per direction) is performed with effective error protection for
standard slaves with a maximum cycle time of 5 ms. Due to the higher number or participants, for
slaves in the extended addressing mode, the cycle time is doubled (
max. 10
ms
) for data sent
from the
slave to the master
. Extended addressing for sending data
to the slave
cause an additional doubling of
the cycle time to
max. 21
ms
.
The AS-Interface cable (yellow) transfers data and power.
Pos: 184 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/AS-Interface [alle Geräte]/Das Bussystem_03 [SK xxxE-FDS] @ 41\mod_1583914005416_388.docx @ 2596575 @ @ 1
It can supply for both the total need of control voltage (including control voltage for the device and any
connected sensors) and only the AS-Interface.
The supply of the device and any connected sensors can also be effected via an internal power supply
unit (“
-HVS
” option), via the “black two-wire line” (only possible with plug connector option: “
-AUX
” or
“
-AXS
” on option slot
M8
), or via a combination of both.
For the “
-AUX
” or “
-AXS
” option, the power supply unit (“
-HVS
” option) takes over a load-reducing
power supply function. For the “
-ASI
” and “
-ASS
” options, it depends on the AS-i supply voltage level.
Therefore, a load reduction cannot be assumed in each case.
“
-AUX
” or “
-AXS
” option (option slot
M8
): It is recommended, but not mandatory to effect the supply
via
P
rotective
E
xtra
L
ow
V
oltage (
PELV
).
Pos: 185 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/AS-Interface [alle Geräte]/Das Bussystem_04 [SK 2xxE-FDS] @ 20\mod_1519208555954_388.docx @ 2406684 @ 5 @ 1