S
ection
4
35
Vent even or below enclosure floor.
621156 Vent.
Distance between the top of the
lower vent opening and bottom of
baffle 4¼ to 4¾ in.
B.ottom baffle.
Top baffle.
¼ - 1 in. clearance max.
¼ - 1 in. clearance max.
Aluminum or galvanized steel sheet baffle
full width of enclosure.
Angle not to exceed 45°.
622293 Roof cap.
616319 Exhaust vent
Fans
Figure 4-3. —Roof venting - Exhaust vent offset inboard of cooling system,
enclosure depth more than 24 in. and less than 26 in.