S
ection
3
Switch okay?
From page 27
Check fans switch.
NO
YES
Refer to Section Cooling System Troubleshooting
chart, Section 8, page ##
Fans okay?
YES
NO
Obstructions blocking air flow
through the enclosure?
NO
YES
Check fans operation.
1. Replace fans.
2. Replace/reset high temperature limit
switch.
3. Test cooling system performance on AC
and LP gas operation.
1. Clear obstructions.
2. Replace/reset high temperature limit switch.
3. Test cooling system performance on AC and LP
gas operation.
1. Replace fan thermostatic switch.
2. Replace/reset high temperature limit
switch.
3. Test cooling system performance on AC
and LP gas operation.