Chapter 6 Functional principle
6.1.2 Overflow module
This module monitors the measurement range limits of the raw value. If a universal input was, for example,
switched to "4-20mA" mode, a raw value of 2mA will violate the measurement range. The overflow module is
only available for the 4 universal inputs in "4-20mA", "0-20mA", "0-2V" und "0-10V"channel modes.
The following table specifies the relevant parameters for the module:
Configuration section
Mode/Interface
Parameter
Explanation
Measurement channels - >
Config
Digital
---
---
Cnt.Inf.
Cnt.Day
Cnt.Intrvl.
4-20mA
Overflow
Procedure in the event of measurement
range violations
0-20mA
0-2V
0-10V
6.1.3 Scale module (inputs)
This module rescales the raw value (e.g. mA) to the required measurement value (e.g. mm). The scale
module is only available for the 4 universal inputs.
The following table specifies the relevant parameters for the module:
Configuration section
Mode
Parameter
Explanation
Measurement channels ->
Basis
Digital
Invert
Inverts the input signal
Cnt.Inf.
Impulse
Metered measurand of a pulse in the "Imp.
unit"
Cnt.Day
Impulse
Counted measurand of a pulse in the
measurement unit
Cnt.Intrvl.
4-20mA
0-20mA
0-2V
0-10V
0%
Start of the measurement range in the
measurement unit
100%
End of the measurement range in the
measurement unit
6.1.4 Trim/sensor offset module
The installation height of the sensor can be taken into consideration with the help of this module. It also
enables the zero point to be adjusted without having to change the value for the installation height again. The
trim/sensor offset module is only available for analogue modes ("0...20mA", "4...20mA", "0-2V", "0-10V"). The
"Trimming" parameter value and the "Sensor offset" parameter value are added to the output value of the
scale module (see "Scale module (inputs)" on page 29). This means that a negative prefix must be set for the
"Trimming" parameter (see "Additional explanation on the zero point adjustment and installation height of the
sensor" on page 79) if the scaled measurement value should be reduced during the zero point adjustment.
NivuLog Easy V3 - Rev. 03 as of 24.10.2018
29 of 141
Содержание NivuLog Easy V3
Страница 2: ...2 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 8: ...8 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 16: ...16 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 20: ...20 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 42: ...42 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 68: ...68 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 110: ...110 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 112: ...112 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 118: ...118 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 120: ...120 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 130: ...130 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 138: ...138 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 140: ...140 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...