Transmission time
Selection of whether a connection to the server should be established every day
at a firmly defined time
Off
No additional transmissions
On
The adjacent option can be used to determine the time at
which the device establishes a connection to the server
regardless of the transmission cycle.
If an additional transmission has been initiated, the internal
meter of the device, that determines the time of the
transmission, is reset. This means that the next
transmission is completed exactly after the time specified
via the "transmission cycle" parameter.
Delay for power off alarm Selection of whether an alarm should be triggered in the event of a supply
voltage failure
Off
No alarm generated in the event of a supply voltage failure
On
A relevant alarm is only triggered if the supply voltage has
failed for longer than the time configured here. This
prevents alarms from being triggered in the event of brief
supply voltage failures. However, an entry is always added
to the device log. If the time is set to 0, an alarm is
generated every time the supply voltage fails.
Record interval
Time between measurement data recordings
Alternative record interval Time between measurement data recordings, if an alternative record interval
should be used because of a trigger being initiated
Measurement cycle
Time between measurements (00:00 same as record interval)
Charge mode
Off
Charge control deactivated
Normal
The charge control is activated and the rechargeable
battery is charged to the maximum voltage if the state of
charge of the rechargeable battery for the power supply
unit falls below 50%. The charge control is then
deactivated again. This is designed to optimise the service
life of the rechargeable battery.
Solar
The rechargeable battery of the power supply unit is
charged to the maximum voltage if the supply or charging
voltage V IN exceeds 16V The charge control then
remains deactivated for 12 hours unless the state of
charge of the rechargeable battery for the power supply
unit drops below 95%. This charge strategy is
recommended if a solar field is used to charge the
rechargeable battery.
Time zone
Regional settings (not relevant for raw measurement data as this is stored in
UTC)
100 of 141
NivuLog Easy V3 - Rev. 03 as of 24.10.2018
Содержание NivuLog Easy V3
Страница 2: ...2 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 8: ...8 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 16: ...16 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 20: ...20 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 42: ...42 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 68: ...68 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 110: ...110 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 112: ...112 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 118: ...118 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 120: ...120 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 130: ...130 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 138: ...138 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 140: ...140 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...