Chapter 10 User interfaces
Note:
Additional explanation: Delta mode
Assumption:
The source channel contains the counter reading of an infinite counter in m
3
. The calculated
channel 1 should contain the flow rate in m
3
/s and calculated channel 2 should contain the flow rate in l/h.
Parameter
Value channel 1 Value channel 2
Basis -> mode
Delta
Delta
Basis -> unit
m
3
/s
l/h
Calculation ->
time basis
Seconds
Hours
Calculation ->
offset
0
0
Calculation ->
factor
1
1000
Required configuration
Source
Calculated channel 1
Calculated channel 2
Date/time
Infinite counter [m
3
]
Flow rate [m
3
/s]
Flow rate [l/h]
26.03.2013 12:50
900
0
1)
0
1)
26.03.2013 12:51
960
1
3,600,000
26.03.2013 12:52
990
0.5
1,800,000
26.03.2013 12:53
1005
0.25
900,000
26.03.2013 12:54
1065
1
3,600,000
1)
Calculation not possible as there is no measurement value before 12:50.
Explanation:
No values can be determined for the measurement at 12:50 for the calculated channels as there
is no previous value and the difference between the counter readings cannot be determined. For the
measurement at 12:51, the difference to the counter reading is 60m
3
and the time difference is 60sec.
Result = { (value difference / time difference [sec.]) * time basis [sec] * factor } + offset
The result for calculated channel 1 (time basis "Seconds", offset "0" and factor "1") is calculated as follows:
Channel 1 = { (60m
3
/ 60sec.) * 1 * 1 } + 0 = 1m
3
/s
The result for calculated channel 2 (time basis "Hours", offset "0" and factor "1000") is calculated as follows:
Channel 2 = { (60m
3
/ 60sec.) * 3600 * 1000 } + 0 = 3,600,000l/h
10.2.1.2.4.3 Alarms
Note:
The evaluation of the alarm thresholds for calculated channels can only occur if the device has
transferred the measurement data to the Device to Web server.
Alarm low
An alarm is triggered, if the measurement value drops to or below this value.
Alarm high
An alarm is triggered, if the measurement value meets or exceeds this value.
Hyst %
Hysteresis for the all-clear in the event of an alarm/warning (e.g. Hyst = 5%, alarm or
warning at 100 -> all-clear at 95) or reset the trigger (e.g. Hyst = 5%, level = greater or
equal, trigger at 100 -> reset at 95)
NivuLog Easy V3 - Rev. 03 as of 24.10.2018
105 of 141
Содержание NivuLog Easy V3
Страница 2: ...2 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 8: ...8 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 16: ...16 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 20: ...20 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 42: ...42 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 68: ...68 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 110: ...110 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 112: ...112 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 118: ...118 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 120: ...120 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 130: ...130 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 138: ...138 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...
Страница 140: ...140 of 141 NivuLog Easy V3 Rev 03 as of 24 10 2018...