Remove the screwdriver and check the mechanical strength of the connection.
Any other clamps are equipped with screw clamp terminals.
Front panel
It is not allowed to remove the front panel.
Tightness of the terminal housing
Water or dirt must not leak into the terminal housing. Seal the housing with the supplied lid
and both screws respectively.
When connecting the transmitter observe the terminal clamp specifications listed below:
Power supply (terminal 1…5):
Spring cage terminal; wire up to 2.5 mm², strand up to 1.5 mm²,
Screwdriver for pushing in, max. blade width 3 mm
Relay (terminal 12…17):
Screw terminals; wire up to 2.5 mm², strand up to 1.5 mm²,
Screwdriver blade width max. 3 mm
Plug connectors with screw terminal connection (terminal 24…54):
Screw terminal connection; wire up to 1.5 mm², strand up to 1.5 mm²,
Screwdriver blade width max. 2.5 mm
Fig. 20-2
Terminal housing, example Ex version