11 TROUBLE SHOOTING - 11.1
Fault Code
No.
Description
Suggested Remedy
th-Fit
16
Faulty thermistor on heatsink
dAtA-F
17
Internal memory fault. (IO)
Press the stop key. If the fault persists, consult you supplier.
4-20 F
18
4-20mA Signal Lost
Check the analog input connection(s).
dAtA-E
19
Internal memory fault. (DSP)
Press the stop key. If the fault persists, consult you supplier.
F-Ptc
21
Motor PTC thermistor trip
Connected motor thermistor over temperature, check wiring connections and motor
FAn-F
22
Cooling Fan Fault (IP66 only)
Check / replace the cooling fan
0-hEAt
23
Drive internal temperature too high
Drive ambient temperature too high, check adequate cooling air is provided
Atf-01
40
Autotune Fault
The motor parameters measured through the autotune are not correct.
Check the motor cable and connections for continuity
Check all three phases of the motor are present and balanced
Atf-02
41
Atf-03
42
Atf-04
43
Atf-05
44
SC-F01
50
Modbus comms loss fault
Check the incoming Modbus RTU connection cable
Check that at least one register is being polled cyclically within the timeout limit set in
P-36 Index 3
SC-F02
51
CANopen comms loss trip
Check the incoming CAN connection cable
Check that cyclic communications take place within the timeout limit set in P-36 Index 3