The use of a suitable gland system is required to maintain the appropriate
IP / Nema rating. The gland plate has pre moulded cable entry holes for
power and motor connections suitable for use with glands as shown in
the following table. Where additional holes are required, these can be
drilled to suitable size. Please take care when drilling to avoid leaving any
particles within the product.
Cable Gland recommended Hole Sizes & types:
Power & Motor Cables
Control & Signal Cables
Moulded Hole Size
Imperial Gland
Metric Gland
Knockout Size
Imperial Gland
Metric Gland
Size 1
22mm
PG13.5
M20
22mm
PG13.5
M20
Size 2 & 3
27mm
PG21
M25
22mm
PG13.5
M20
Flexible Conduit Hole Sizes:
Drill Size
Trade Size
Metric
Size 1
28mm
¾ in
21
Size 2 & 3
35mm
1 in
27
• UL rated ingress protection ("Type" ) is only met when cables are installed using a UL recognized bushing or fitting for a flexible-conduit system which meets the required level
of protection ("Type")
• For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC
• Not intended for installation using rigid conduit system
Power Isolator Lock Off
On the switched models the main power isolator switch can be locked in the ‘Off’ position using a 20mm standard shackle padlock (not supplied).
IP66 / Nema 4X Gland Plate
IP66 / Nema 4X Unit Lock Off