AD700E
35
General information
Important safety information
General Information and Ratings
Mechanical Installation
Operation
Parameters
Analog and Digital Input Macro
Configurations
Power Wiring
Chapter 9
P. 48
Chapter 10
P. 50
Modbus RTU Communications
Technical Data
Trouble Shooting
Chapter 11
P. 54
PREVIOUS VIEW
3/6
7
7.2 EXTENDED P
ARAMETERS
Par
Description
Minimum
Maximum
Default
Units
P-30
Start Mode & Automatic Restart
N/A
N/A
Edge-r
-
Selects whether the drive should start automatically if the enable input is present and latched during power on. Also configures the Automatic
Restart function.
Ed93-r
: Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a power on or
reset to start the drive.
AUto-0
: Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed.
AUto-1
to
AUto-5
: Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals. The numbers of restart attempts
are counted, and if the drive fails to start on the final attempt, the drive will trip with a fault, and will require the user to manually reset the
fault. The drive must be powered down to reset the counter.
P-31
Keypad Start Mode Select
0
7
1
-
This parameter is active only when operating in Keypad Control Mode (P-12 = 1 or 2) or Modbus Mode (P-12 = 3 or 4). When settings 0 or 1
are used, the Keypad Start and Stop keys are active, and control terminals 1 and 2 must be linked together. Settings 2 and 3 allow the drive to
be started from the control terminals directly, and the keypad Start and Stop keys are ignored.
0 : Minimum Speed, Keypad Start
1 : Previous Speed, Keypad Start
2 : Minimum Speed, Terminal Enable
3 : Previous Speed, Terminal Enable
4 : Current Speed, Keypad Start
5 : Preset Speed 4, Keypad Start
6 : Current Speed, Terminal Start
7 : Preset Speed 4, Terminal Start
P-32
Index 1 : Duration
0.0
25.0
0.0
s
Index 2 : DC Injection Mode
0
2
0
-
Index 1:
Defines the time for which a DC current is injected into the motor. DC Injection current level may be adjusted in P-59.
Index 2 :
Configures the DC Injection Function as follows :
0 : DC Injection on Stop.
DC is injected into the motor at the current level set in P-59 following a stop command, after the output frequency
has reached 0.0Hz for the time set in Index 1. This can be useful to ensure the motor has reached a complete stop before the drive disables.
Note If the drive is in Standby Mode prior to disable, the DC injection is disabled
1 : DC Injection on Start.
DC is injected into the motor at the current level set in P-59 for the time set in Index 1 immediately after the drive is
enabled, prior to the output frequency ramping up. The output stage remains active during this phase. This can be used to ensure the motor is
at standstill prior to starting.
2 : DC Injection on Start & Stop.
DC injection applied as both settings 0 and 1 above.
P-33
Spin Start
0
2
0
-
0 : Disabled
1 : Enabled.
When enabled, on start up the drive will attempt to determine if the motor is already rotating, and will begin to control the motor
from its current speed. A short delay may be observed when starting motors which are not turning.
2 : Enabled on Trip, Brown Out or Coast Stop.
Spin start is only activated following the events listed, otherwise it is disabled.