AD700E
48
General information
Important safety information
General Information and Ratings
Mechanical Installation
Operation
Parameters
Analog and Digital Input Macro
Configurations
Power Wiring
Chapter 9
P. 48
Chapter 10
P. 50
Modbus RTU Communications
Technical Data
Trouble Shooting
Chapter 11
P. 54
PREVIOUS VIEW
9 MODBUS RTU COMMUNICATIONS
9.1 INTRODUCTION
The AD700E can be connected to a Modbus RTU network via the RJ45
connector on the front of the drive.
9.2 MODBUS RTU SPECIFICATION
9.3 RJ45 CONNECTOR CONFIGURATION
For full MODBUS RTU register map information please refer to your
NIDEC representative. Local contacts can be found by visiting our website
www.nidec-industrial.com
When using MODBUS control the Analog and Digital Inputs
can be configured as shown in section 9.5
9.4 MODBUS TELEGRAM STRUCTURE
The AD700E supports Master / Slave Modbus RTU communications,
using the 03 Read Holding Registers and 06 Write Single Holding Register
commands. Many Master devices treat the first Register address as
Register 0, therefore it may be necessary to convert the Register Numbers
detail in section 9.5 by subtracting 1 to obtain the correct Register
address. The telegram structure is as follows:
9 MODBUS R
TU COMMUNICA
TIONS - 9.1 - 9.2 - 9.3 - 9.4
9
Protocol
Modbus RTU
Error check
CRC
Baud rate
9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default)
Data format
1 start bit, 8 data bits, 1 stop bits, no parity.
Physical signal
RS 485 (2-wire)
User interface
RJ45
Command 03 – Read Holding Registers
Master Telegram
Length
Slave Response
Length
Slave Address
1
Byte
Slave Address
1
Byte
Function Code (03)
1
Byte
Starting Address
1
Byte
1
st
Register Address
2
Bytes
1
st
Register Value
2
Bytes
No. Of Registers
2
Bytes
2
nd
Register Value
2
Bytes
CRC Checksum
2
Bytes
Etc...
CRC Checksum
2
Bytes
Command 06 – Write Single Holding Register
Master Telegram
Length
Slave Response
Length
Slave Address
1
Byte
Slave Address
1
Byte
Function Code (06)
1
Byte
Function Code (06) 1
Byte
Register Address
2
Bytes
Register Address
2
Bytes
Value
2
Bytes
Register Value
2
Bytes
CRC Checksum
2
Bytes
CRC Checksum
2
Bytes
1
No Connection
2
No Connection
3
0 Volts
4
-RS485 (PC)
5
+RS485 (PC)
6
+24 Volt
7
-RS485 (Modbus RTU)
8
+RS485 (Modbus RTU)
Warning:
This is not an Ethernet
connection. Do not connect
directly to an Ethernet port.