4.6 GUIDELINES FOR MOUNTING (IP66 UNITS)
4
4.6 GUIDELINES FOR MOUNTING (IP66 UNITS)
• Before mounting the drive, ensure that the chosen location meets the
environmental condition requirements for the drive shown in section 10.1
• The drive must be mounted vertically, on a suitable flat surface
• The minimum mounting clearances as shown in the table below must be
observed
• The mounting site and chosen mountings should be sufficient to support
the weight of the drives
• Using the drive as a template, or the dimensions shown above, mark the
locations required for drilling
• Suitable cable glands to maintain the ingress protection of the drive are
required. Gland holes for power and motor cables are pre-moulded into
the drive enclosure, recommended gland sizes are shown above. Gland
holes for control cables may be cut as required.
NOTE:
Typical drive heat losses are approximately 3% of operating load
conditions.
Above are guidelines only and the operating ambient temperature of the
drive MUST be maintained at all times.
Drive Size
X Above & Below
Y Either Side
mm
in
mm
in
1
200
7.87
10
0.39
2
200
7.87
10
0.39
3
200
7.87
10
0.39
Cable Gland Sizes
Drive Size
Power Cable
Motor Cable
Control Cables
1
M20 (PG13.5)
M20 (PG13.5)
M20 (PG13.5)
2
M25 (PG21)
M25 (PG21)
M20 (PG13.5)
3
M25 (PG21)
M25 (PG21)
M20 (PG13.5)