7.2 EXTENDED PARAMETERS
7.2 EXTENDED P
ARAMETERS
Par
Description
Minimum
Maximum
Default
Units
P-15
Digital Input Function Select
0
17
0
-
Defines the function of the digital inputs depending on the control mode setting in P-12. See section 8 Analog and Digital Input Macro
Configurations for more information.
P-16
Analog Input 1 Signal Format
See Below
U0-10
-
U 0-10
= 0 to 10 Volt Signal (Uni-polar). The drive will remain at 0.0Hz if the analog reference after scaling and offset are applied is =<0.0%
b 0-10
= 0 to 10 Volt Signal, bi-directional operation. The drive will operate the motor in the reverse direction of rotation if the analog reference
after scaling and offset are applied is <0.0%. E.g. for bidirectional control from a 0 – 10 volt signal, set P-35 = 200.0%, P-39 = 50.0%
A 0-20
= 0 to 20mA Signal
t 4-20
= 4 to 20mA Signal, the Answer Drives will trip and show the fault code
4-20f
if the signal level falls below 3mA
r 4-20
= 4 to 20mA Signal, the Answer Drives will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
t 20-4
= 20 to 4mA Signal, the Answer Drives will trip and show the fault code
4-20f
if the signal level falls below 3mA
r 20-4
= 20 to 4mA Signal, the Answer Drives will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
U 10-0
= 10 to 0 Volt Signal (Uni-polar). The drive will operate at Maximum Frequency / Speed if the analog reference after scaling and offset
are applied is =<0.0%
P-17
Maximum Effective Switching
Frequency
4
32
8 / 16
kHz
Sets maximum effective switching frequency of the drive. If “rEd” is displayed, the switching frequency has been reduced to the level in P00-32
due to excessive drive heatsink temperature.
P-18
Output Relay Function Select
0
7
1
-
Selects the function assigned to the relay output. The relay has two output terminals, Logic 1 indicates the relay is active, and therefore
terminals 10 and 11 will be connected.
0 : Drive Enabled (Running).
Logic 1 when the motor is enabled
1 : Drive Healthy.
Logic 1 when power is applied to the drive and no fault exists
2 : At Target Frequency (Speed).
Logic 1 when the output frequency matches the setpoint frequency
3 : Drive Tripped.
Logic 1 when the drive is in a fault condition
4 : Output Frequency >= Limit.
Logic 1 when the output frequency exceeds the adjustable limit set in P-19
5 : Output Current >= Limit.
Logic 1 when the motor current exceeds the adjustable limit set in P-19
6 : Output Frequency < Limit.
Logic 1 when the output frequency is below the adjustable limit set in P-19
7 : Output Current < Limit.
Logic 1 when the motor current is below the adjustable limit set in P-19
8 : Analog Input 2 > Limit.
Logic 1 when the signal applied to analog input 2 exceeds the adjustable limit set in P-19
9 : Drive Ready to Run.
Logic 1 when the drive is ready to run, no trip present.
P-19
Relay Threshold Level
0.0
200.0
100.0
%
Adjustable threshold level used in conjunction with settings 4 to 8 of P-18