PREVIOUS VIEW
10 TECHNICAL DA
TA - 10.1
10
10 TECHNICAL DATA
10.1 ENVIRONMENTAL
Operational ambient temperature range Open Drives:
-10 … 50°C (frost and condensation free)
Enclosed Drives: -10 ... 40°C (frost and condensation free)
Storage ambient temperature range:
-40 … 60°C
Maximum altitude:
2000m. Derate above 1000m : 1% / 100m
Maximum humidity:
95%, non-condensing
NOTE:
For UL compliance: the average ambient temperature over a 24 hour period for 200-240V, 2.2kW and 3HP, IP20 drives is 45°C.