INSTALLATION

3

 

INSTALLATION

3.1  PRE-INSTALLATION CHECKS

Before proceeding with the product’s installation, it is necessary 

to:

 

check the integrity of the supply

 

check that all the materials are in good working order and 

suited to the intended use

 

check that all operating conditions comply with that specified 

in the “

Product usage limits

”  paragraph  and  in  the  “

TECHNICAL SPECIFICATIONS

” chapter

 

check that the chosen installation location is compatible with 

the product’s overall dimensions (see “

Figure

 

2

”)

 

check that the surface chosen for installing the product is 

solid and can ensure stable attachment

 

make sure that the installation area is not subject to flooding; if 

necessary, the product must be installed appropriately raised 

above ground level

 

check that the space around the product allows safe and easy 

access

 

check that all electrical cables to be used belong to the type 

listed in “

Table 1

 

check that the automation has mechanical stops in both the 

opening and closing phases.

3.2  PRODUCT USAGE LIMITS

The product must be used exclusively with the gearmotors listed 

in “

Table 4

” and in accordance with the corresponding usage 

limits.

These motors are reversible, which means that the gate leaves 

can be moved manually without having to manually unlock the 

gearmotor. By means of a sensor inserted in the motor, the 

control unit can detect the manual movement of the leaves and, 

moreover, correctly perform the successive operations, thus 

preventing the two leaves from striking the opening and closing 

mechanical stops.

IMPORTANT: if the “Stand-by all” function is active, 

the manual movement of the leaves is not detected.

3.3  PRODUCT IDENTIFICATION AND OVERALL 

DIMENSIONS

The overall dimensions and label (A) that allow for identifying the 

product are shown in “

Figure

 

2

”.

232 mm

310 mm

122 mm

A

2

3.4  TYPICAL INSTALLATION

Figure

 

3

”  shows  an  example  of  an  automation  system 

constructed using 

Nice

 components.

D

D

G

G

B

H

B

E

A

F

F

C

I

3

Control unit

Gearmotor

Warning light

Photocell

Digital keypad - Transponder reader - Key selector

Photocell column

Mechanical stops for the open position

Mechanical stop at closed position

Electric lock

These above-mentioned components are positioned according 

to a typical standard layout. Using the layout in “

Figure

 

4

” as 

a  reference,  define  the  approximate  position  in  which  each 

component of the system will be installed.

Before proceeding with the installation, prepare 

the required electrical cables by referring to 

Figure  4” and to that stated in the “TECHNICAL 

SPECIFICATIONS” chapter.

b c

a

d

g

f-h

d

d

e

d

4

Table 1

TECHNICAL SPECIFICATIONS OF ELECTRICAL CABLES

Identification 

no.

Cable characteristics

a

CONTROL UNIT POWER SUPPLY cable

1 cable 3 x 1.5 mm

2

Maximum length 30 m [

note 1

]

b

WARNING LIGHT cable

1 cable 2 x 0.5 mm

2

Maximum length 20 m

c

ANTENNA cable

1 x RG58-type shielded cable

Maximum length 20 m; recommended < 5 m

d

BLUEBUS DEVICES cable

1 cable 2 x 0.5 mm

2

Maximum length 20 m [

note 2

]

e

KEY SELECTOR cable

2 cables 2 x 0.5 mm

2

Maximum length 50 m [

note 3

]

Содержание MC824HR

Страница 1: ...Nice MC824HR Control unit EN Instructions and warnings for installation and use...

Страница 2: ...handle the product with care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these actions can dam...

Страница 3: ...paragraph and an IBT4N type connector which through the IBT4N interface can be used to connect BusT4 devices such as the Oview programmer see the Connecting the IBT4N interface paragraph The control u...

Страница 4: ...form the successive operations thus preventing the two leaves from striking the opening and closing mechanical stops m IMPORTANT if the Stand by all function is active the manual movement of the leave...

Страница 5: ...ectronic circuits 3 5 INSTALLING THE CONTROL UNIT a Secure the control unit to an unmovable vertical flat surface adequately protected against possible impacts The lower part of the control unit must...

Страница 6: ...y III overvoltage conditions in accordance with the installation instructions If necessary this device guarantees quick and safe disconnection from the mains power and therefore must be positioned in...

Страница 7: ...ed resistor output such as sensitive edges can be connected to this input Each device connected to this input will be individually recognised by the control unit during the learning phase see Learning...

Страница 8: ...opening stops and restarts when the photocell disengages PHOTOCELL ADDRESSES Photocell Position of the jumpers FOTO 2 PHOTO 2 Internal photocell triggered during the opening phase stops and reverses t...

Страница 9: ...m closing This procedure can be carried out in three different ways automatic manual and mixed In automatic mode the control unit learns the mechanical stops calculates the most appropriate gate leaf...

Страница 10: ...on to stop the learning phase At this point invert the control wires external positions with respect to the terminal on the motor that executed the opening manoeuvre and repeat the self learning proce...

Страница 11: ...button is released LED L7 will start flashing 9 LED L7 flashes position 1 of M1 to command and move motor 1 to position 1 Figure 14 press and hold the f or h button Once the position is reached relea...

Страница 12: ...y whether the leaves can be opened and closed with a force below 390 N 3 lock the motors as described in the respective instruction manual 4 using the control devices transmitter control button key se...

Страница 13: ...2 release the g button when LED L1 starts flashing 3 press the f or h button to move the flashing LED to the LED associated with the function to be modified 4 press the g button to change the status...

Страница 14: ...TABLE PARAMETERS All the Level 2 parameters are factory set as highlighted in GREY in Table 7 and can be modified at any time The parameters can be set to a scale of 1 to 8 The check the value corresp...

Страница 15: ...executed if the sent command remains if the command is interrupted the manoeuvre stops L8 Semi automatic opening hold to run closing L3 Motor speed L1 Very slow Adjusts the motor speed during normal t...

Страница 16: ...roceed with point 2 2 within 3 seconds press the control again and hold it down 3 after roughly 2 seconds the gate will complete the requested manoeuvre in hold to run mode in other words it will cont...

Страница 17: ...stance Verify the cause and increase the motor force if necessary 4 short flashes 1 second pause 4 short flashes Intervention of the STOP input At the start of the manoeuvre or during the movement its...

Страница 18: ...blown verify the cause and replace it with one having the same characteristics Green LED always on Serious anomaly There is a serious problem try disconnecting the power supply to the control unit an...

Страница 19: ...ton to shift flashing of the LED to L8 Anomaly list parameter 4 keep the g button pressed down it must be kept pressed throughout phases 5 and 6 5 wait roughly 3 seconds after which LED L1 correspondi...

Страница 20: ...mation Unlock or only from Oview the following commands Unlock and close and Unlock and open 12 Lock automation Triggers the stoppage of the manoeuvre and locks the automation the control unit will no...

Страница 21: ...CT MAINTENANCE Being an electronic part the control unit does not require any special maintenance Nonetheless the system should be regularly checked to ensure that it works efficiently at least every...

Страница 22: ...us triggers the STOP command SbS input for normally open contacts the closing of the contact triggers the Step by Step command OPEN input for normally open contacts the closing of the contact triggers...

Страница 23: ...ding to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to machinery and amending...

Страница 24: ...24 ENGLISH NOTES...

Страница 25: ...y but contact your trusted installer l Do not modify the system or the programming and adjustment parameters of the control unit your installer is exclusively responsible for these operations Failure...

Страница 26: ...26 ENGLISH NOTES...

Страница 27: ...ENGLISH 27 NOTES...

Страница 28: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0133A01EN_15 01 2019...

Отзывы: