background image

12 

– ENGLISH

4.9  CHECKING THE GATE MOVEMENT

At the end of the learning phase, we recommend letting the 

control unit run a few opening and closing manoeuvres to verify 

whether the gate moves correctly and if there are any assembly 

and adjustment defects.

18

1. 

To do this:

2. 

press the 

f

 button (“

Figure

 

18

”).  Check  that 

the acceleration, constant-speed and slowdown phases 

are present during the opening manoeuvre. Once the 

manoeuvre terminates, the gate leaves must stop a few 

centimetres from the opening mechanical stop

3. 

press the 

h

 button (“

Figure

 

18

”) and verify that 

the acceleration, constant-speed and slowdown phases 

are present during the closing manoeuvre. Once the 

manoeuvre terminates, the gate leaves must be perfectly 

closed on the closing mechanical stop

4. 

check that all the previously adjusted functions have been 

learned by the control unit.

TESTING AND COMMISSIONING

5

 

TESTING AND COMMISSIONING

These are the most important phases of the automation’s 

construction, as they ensure maximum safety of the system. The 

test can also be used to periodically verify the devices making 

up the automation.

Testing and commissioning of the automation must 

be  performed  by  skilled  and  qualified  personnel, 

who are responsible for the tests required to 

verify the solutions adopted according to the risks 

present, and for ensuring that all legal provisions, 

standards and regulations are met, in particular 

all the requirements of the EN 12445 standard, 

which defines the test methods for checking gate 

automations.

The additional devices must undergo specific testing, both in 

terms of their functions and their proper interaction with the 

control unit. Refer to the instruction manuals of the individual 

devices.

5.1  TESTING

The sequence of steps to be performed when running the 

testing phase, as described below, refers to a typical system 

(“

Figure

 

3

”).

To run the test:

1. 

verify that all the instructions stated in the “

GENERAL 

SAFETY WARNINGS AND PRECAUTIONS

”  chapter 

have been strictly observed

2. 

unlock the motors for the manual manoeuvre as described 

in the respective instruction manual. Move the gate 

manually and verify whether the leaves can be opened 

and closed with a force below 390 N

3. 

lock the motors as described in the respective instruction 

manual

4. 

using the control devices (transmitter, control button, 

key selector, etc.), test the gate’s opening, closing and 

stoppage movements to make sure that the leaves move 

as intended. Several tests should be carried out to assess 

the movement of the leaves and detect any defects in 

the installation and adjustment, besides any points of 

excessive friction

5. 

verify the correct operation of all the safety devices 

present, one by one (photocells, sensitive edges, etc.). If 

a device intervenes, the “

Bluebus

” (

A

 - “

Figure

 

11

”) LED 

on the control unit will emit two quick flashes to confirm

6. 

if potentially dangerous situations due to the movement 

of the leaves have been prevented by limiting the impact 

force, the latter must be measured according to the EN 

12445 standard and, if the “motor force” control is used to 

aid the system in reducing the impact force, it is necessary 

to test various adjustments to find the one that gives the 

best results.

5.2  COMMISSIONING

Commissioning can only be performed after all 

testing phases have been successfully completed.

Before commissioning the automation, ensure that 

the owner is properly informed of all residual risks 

and hazards.

To commission the automation:

1. 

compile  the  automation’s  technical  file,  which  must 

include the following documents: overall drawing of the 

automation, wiring diagram, risk assessment and relative 

solutions adopted, the manufacturer’s declaration of 

conformity for all devices used and the declaration of 

conformity compiled by the installer

2. 

affix  a  data  plate  on  the  gate  specifying  at  least  the 

following data: type of automation, name and address of 

the manufacturer (responsible for commissioning), serial 

number, year of manufacture and CE mark

3. 

compile the declaration of conformity of the automation 

and hand it to the owner of the automation

4. 

compile the User Manual of the automation and hand it to 

the owner of the automation

5. 

compile and provide the owner with the automation’s 

“Maintenance  schedule”,  containing  the  maintenance 

instructions for all the automation’s devices.

For all the above-mentioned documentation, Nice – 

through its technical assistance service – provides 

the following: pre-completed forms.

Содержание MC824HR

Страница 1: ...Nice MC824HR Control unit EN Instructions and warnings for installation and use...

Страница 2: ...handle the product with care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these actions can dam...

Страница 3: ...paragraph and an IBT4N type connector which through the IBT4N interface can be used to connect BusT4 devices such as the Oview programmer see the Connecting the IBT4N interface paragraph The control u...

Страница 4: ...form the successive operations thus preventing the two leaves from striking the opening and closing mechanical stops m IMPORTANT if the Stand by all function is active the manual movement of the leave...

Страница 5: ...ectronic circuits 3 5 INSTALLING THE CONTROL UNIT a Secure the control unit to an unmovable vertical flat surface adequately protected against possible impacts The lower part of the control unit must...

Страница 6: ...y III overvoltage conditions in accordance with the installation instructions If necessary this device guarantees quick and safe disconnection from the mains power and therefore must be positioned in...

Страница 7: ...ed resistor output such as sensitive edges can be connected to this input Each device connected to this input will be individually recognised by the control unit during the learning phase see Learning...

Страница 8: ...opening stops and restarts when the photocell disengages PHOTOCELL ADDRESSES Photocell Position of the jumpers FOTO 2 PHOTO 2 Internal photocell triggered during the opening phase stops and reverses t...

Страница 9: ...m closing This procedure can be carried out in three different ways automatic manual and mixed In automatic mode the control unit learns the mechanical stops calculates the most appropriate gate leaf...

Страница 10: ...on to stop the learning phase At this point invert the control wires external positions with respect to the terminal on the motor that executed the opening manoeuvre and repeat the self learning proce...

Страница 11: ...button is released LED L7 will start flashing 9 LED L7 flashes position 1 of M1 to command and move motor 1 to position 1 Figure 14 press and hold the f or h button Once the position is reached relea...

Страница 12: ...y whether the leaves can be opened and closed with a force below 390 N 3 lock the motors as described in the respective instruction manual 4 using the control devices transmitter control button key se...

Страница 13: ...2 release the g button when LED L1 starts flashing 3 press the f or h button to move the flashing LED to the LED associated with the function to be modified 4 press the g button to change the status...

Страница 14: ...TABLE PARAMETERS All the Level 2 parameters are factory set as highlighted in GREY in Table 7 and can be modified at any time The parameters can be set to a scale of 1 to 8 The check the value corresp...

Страница 15: ...executed if the sent command remains if the command is interrupted the manoeuvre stops L8 Semi automatic opening hold to run closing L3 Motor speed L1 Very slow Adjusts the motor speed during normal t...

Страница 16: ...roceed with point 2 2 within 3 seconds press the control again and hold it down 3 after roughly 2 seconds the gate will complete the requested manoeuvre in hold to run mode in other words it will cont...

Страница 17: ...stance Verify the cause and increase the motor force if necessary 4 short flashes 1 second pause 4 short flashes Intervention of the STOP input At the start of the manoeuvre or during the movement its...

Страница 18: ...blown verify the cause and replace it with one having the same characteristics Green LED always on Serious anomaly There is a serious problem try disconnecting the power supply to the control unit an...

Страница 19: ...ton to shift flashing of the LED to L8 Anomaly list parameter 4 keep the g button pressed down it must be kept pressed throughout phases 5 and 6 5 wait roughly 3 seconds after which LED L1 correspondi...

Страница 20: ...mation Unlock or only from Oview the following commands Unlock and close and Unlock and open 12 Lock automation Triggers the stoppage of the manoeuvre and locks the automation the control unit will no...

Страница 21: ...CT MAINTENANCE Being an electronic part the control unit does not require any special maintenance Nonetheless the system should be regularly checked to ensure that it works efficiently at least every...

Страница 22: ...us triggers the STOP command SbS input for normally open contacts the closing of the contact triggers the Step by Step command OPEN input for normally open contacts the closing of the contact triggers...

Страница 23: ...ding to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to machinery and amending...

Страница 24: ...24 ENGLISH NOTES...

Страница 25: ...y but contact your trusted installer l Do not modify the system or the programming and adjustment parameters of the control unit your installer is exclusively responsible for these operations Failure...

Страница 26: ...26 ENGLISH NOTES...

Страница 27: ...ENGLISH 27 NOTES...

Страница 28: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0133A01EN_15 01 2019...

Отзывы: