18 

– ENGLISH

7.2  SIGNALS ON THE CONTROL UNIT

The control unit has LEDs “

L1-L8

” on the buttons and LEDs “

L9-

L13

” on the control unit terminals (“

Figure

 

22

”).

Each of these LEDs can emit special signals both during normal 

operation and in case on anomalies. “

Table 10

 and 

Table 11

” 

describe the cause and possible solution for each type of 

anomaly.

Close

Open

SbS

Stop

Bluebus

11 12

L1 L8

..

Close

Open

SbS

Stop

Bluebus

8 9 10 11 12

L9

L10

L11

L12

L13

22

Table 10

SIGNALS OF THE LEDS ON THE CONTROL UNIT TERMINALS

Status

Meaning

Possible solution

All LEDs

No LED is lit

No power to the control unit

Check whether the control unit is powered.

Check that the fuse (

T

 - “

Figure

 

1

”) has not blown. If the fuse has blown, 

verify the cause and replace it with one having the same characteristics.

If also the “

BlueBus

” LED is not lit or flashing, there probably is a serious 

fault that requires the control unit to be replaced.

BLUEBUS LED

Green LED always off

Anomaly

Check whether the control unit is powered.

Check that the fuse (

T

 - “

Figure

 

1

”) has not blown. If the fuse has blown, 

verify the cause and replace it with one having the same characteristics.

Green LED always on

Serious anomaly

There is a serious problem: try disconnecting the power supply to the 

control unit and if the condition persists, replace the electronic board.

1 flash per second of the 

green LED

Everything normal

Normal control unit operation.

2 fast flashes of the 

green LED

Variation of the status of the 

inputs

This is normal if there is a change in one of the “SbS”, “Stop”, “Open” 

or “Close” inputs, the control photocells intervene or a command is 

transmitted with a transmitter.

Series of flashes of the 

red LED divided by a 

1-second pause

Various

Refer to that shown in “

Table 4

”.

STOP LED
OFF

Intervention of the “Stop” 

input

Check the devices connected to the “Stop” input.

On

All OK

“Stop” input active.

SbS LED

OFF

All OK

“SbS” input not active.

On

Intervention of the “SbS” 

input

Normal if the device connected to the “SbS” input is active.

OPEN LED

OFF

Everything normal

“Open” input not active.

On

Intervention of the “Open” 

input

This is normal if the device connected to the “Open” input is active.

CLOSE LED

OFF

Everything normal

“Close” input not active.

On

Intervention of the “Close” 

input

This is normal if the device connected to the “Close” input is active.

Содержание MC824HR

Страница 1: ...Nice MC824HR Control unit EN Instructions and warnings for installation and use...

Страница 2: ...handle the product with care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these actions can dam...

Страница 3: ...paragraph and an IBT4N type connector which through the IBT4N interface can be used to connect BusT4 devices such as the Oview programmer see the Connecting the IBT4N interface paragraph The control u...

Страница 4: ...form the successive operations thus preventing the two leaves from striking the opening and closing mechanical stops m IMPORTANT if the Stand by all function is active the manual movement of the leave...

Страница 5: ...ectronic circuits 3 5 INSTALLING THE CONTROL UNIT a Secure the control unit to an unmovable vertical flat surface adequately protected against possible impacts The lower part of the control unit must...

Страница 6: ...y III overvoltage conditions in accordance with the installation instructions If necessary this device guarantees quick and safe disconnection from the mains power and therefore must be positioned in...

Страница 7: ...ed resistor output such as sensitive edges can be connected to this input Each device connected to this input will be individually recognised by the control unit during the learning phase see Learning...

Страница 8: ...opening stops and restarts when the photocell disengages PHOTOCELL ADDRESSES Photocell Position of the jumpers FOTO 2 PHOTO 2 Internal photocell triggered during the opening phase stops and reverses t...

Страница 9: ...m closing This procedure can be carried out in three different ways automatic manual and mixed In automatic mode the control unit learns the mechanical stops calculates the most appropriate gate leaf...

Страница 10: ...on to stop the learning phase At this point invert the control wires external positions with respect to the terminal on the motor that executed the opening manoeuvre and repeat the self learning proce...

Страница 11: ...button is released LED L7 will start flashing 9 LED L7 flashes position 1 of M1 to command and move motor 1 to position 1 Figure 14 press and hold the f or h button Once the position is reached relea...

Страница 12: ...y whether the leaves can be opened and closed with a force below 390 N 3 lock the motors as described in the respective instruction manual 4 using the control devices transmitter control button key se...

Страница 13: ...2 release the g button when LED L1 starts flashing 3 press the f or h button to move the flashing LED to the LED associated with the function to be modified 4 press the g button to change the status...

Страница 14: ...TABLE PARAMETERS All the Level 2 parameters are factory set as highlighted in GREY in Table 7 and can be modified at any time The parameters can be set to a scale of 1 to 8 The check the value corresp...

Страница 15: ...executed if the sent command remains if the command is interrupted the manoeuvre stops L8 Semi automatic opening hold to run closing L3 Motor speed L1 Very slow Adjusts the motor speed during normal t...

Страница 16: ...roceed with point 2 2 within 3 seconds press the control again and hold it down 3 after roughly 2 seconds the gate will complete the requested manoeuvre in hold to run mode in other words it will cont...

Страница 17: ...stance Verify the cause and increase the motor force if necessary 4 short flashes 1 second pause 4 short flashes Intervention of the STOP input At the start of the manoeuvre or during the movement its...

Страница 18: ...blown verify the cause and replace it with one having the same characteristics Green LED always on Serious anomaly There is a serious problem try disconnecting the power supply to the control unit an...

Страница 19: ...ton to shift flashing of the LED to L8 Anomaly list parameter 4 keep the g button pressed down it must be kept pressed throughout phases 5 and 6 5 wait roughly 3 seconds after which LED L1 correspondi...

Страница 20: ...mation Unlock or only from Oview the following commands Unlock and close and Unlock and open 12 Lock automation Triggers the stoppage of the manoeuvre and locks the automation the control unit will no...

Страница 21: ...CT MAINTENANCE Being an electronic part the control unit does not require any special maintenance Nonetheless the system should be regularly checked to ensure that it works efficiently at least every...

Страница 22: ...us triggers the STOP command SbS input for normally open contacts the closing of the contact triggers the Step by Step command OPEN input for normally open contacts the closing of the contact triggers...

Страница 23: ...ding to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to machinery and amending...

Страница 24: ...24 ENGLISH NOTES...

Страница 25: ...y but contact your trusted installer l Do not modify the system or the programming and adjustment parameters of the control unit your installer is exclusively responsible for these operations Failure...

Страница 26: ...26 ENGLISH NOTES...

Страница 27: ...ENGLISH 27 NOTES...

Страница 28: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0133A01EN_15 01 2019...

Отзывы: