ENGLISH – 

5

TECHNICAL SPECIFICATIONS OF ELECTRICAL CABLES

Identification 

no.

Cable characteristics

f

MOTOR POWER SUPPLY cable

1 cable 3 x 1.5 mm

2

Maximum length 10 m [

note 4

]

g

ELECTRIC LOCK CONNECTION cable

1 cable 2 x 1 mm

2

Maximum length 10 m

h

ENCODER CONNECTION cable

1 cable 2 x 1 mm

2

Maximum length 10 m [

note 4

]

Note 1

  If the power supply cable is longer than 30 m, a cable 

with larger cross-sectional area (3 x 2.5 mm

2

) must be 

used and a safety earthing system must be installed 

near the automation.

Note 2

  If the BlueBus cable is longer than 20 m, up to maximum 

40 m, a cable with larger gauge (2 x 1 mm

2

) must be 

used.

Note 3

  These two cables can be replaced by a single 4 x 0.5 

mm

2

 cable.

Note 4

  These cables can be replaced by a single 5 x 1.5 mm

2

 

cable.

The cables used must be suited to the type of 

environment of the installation site.

When laying the ducting for routing the electrical 

cables and for the cable entry point into the 

control unit housing, check that there are no water 

deposits in the junction wells nor condensate in the 

connection ducts, as water and damp conditions 

could damage the product’s electronic circuits.

3.5  INSTALLING THE CONTROL UNIT

Secure the control unit to an unmovable, vertical, 

flat surface adequately protected against possible 

impacts. The lower part of the control unit must be 

at least 40 cm above the ground.

The control unit is also suitable for being installed 

outdoors, as it is supplied in a container that, if 

adequately installed, guarantees an IP54 protection 

rating.

To secure the control unit (“

Figure

 

5

” and “

Figure

 

6

”):

1. 

loosen the screws (

A

) and remove the cover (

B

) of the 

control unit

2. 

identify the pre-cut holes (

C

) located along the lower 

side of the box and perforate the ones used to pass the 

electrical cables

The side cable entry (D) can only be used if the 

control unit is installed indoors, in a protected 

environment.

B

D

A

C

5

3. 

drill the wall (

E

) by observing the measurements shown in 

the figure and arrange suitable wall plugs (not supplied)

4. 

position the box (

F

) and fasten it with the screws (

G

) (not 

supplied)

5. 

arrange cable glands for passing the connecting cables

6. 

make the electrical connections by operating as described 

in the “

ELECTRICAL CONNECTIONS

” chapter.

To install any other devices used on the automated 

system, refer to the respective instruction manuals.

7. 

after making the electrical connections, put the cover (

B

back on and tighten the screws (

A

).

205 mm

237 mm

E

G

F

6

Содержание MC824HR

Страница 1: ...Nice MC824HR Control unit EN Instructions and warnings for installation and use...

Страница 2: ...handle the product with care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these actions can dam...

Страница 3: ...paragraph and an IBT4N type connector which through the IBT4N interface can be used to connect BusT4 devices such as the Oview programmer see the Connecting the IBT4N interface paragraph The control u...

Страница 4: ...form the successive operations thus preventing the two leaves from striking the opening and closing mechanical stops m IMPORTANT if the Stand by all function is active the manual movement of the leave...

Страница 5: ...ectronic circuits 3 5 INSTALLING THE CONTROL UNIT a Secure the control unit to an unmovable vertical flat surface adequately protected against possible impacts The lower part of the control unit must...

Страница 6: ...y III overvoltage conditions in accordance with the installation instructions If necessary this device guarantees quick and safe disconnection from the mains power and therefore must be positioned in...

Страница 7: ...ed resistor output such as sensitive edges can be connected to this input Each device connected to this input will be individually recognised by the control unit during the learning phase see Learning...

Страница 8: ...opening stops and restarts when the photocell disengages PHOTOCELL ADDRESSES Photocell Position of the jumpers FOTO 2 PHOTO 2 Internal photocell triggered during the opening phase stops and reverses t...

Страница 9: ...m closing This procedure can be carried out in three different ways automatic manual and mixed In automatic mode the control unit learns the mechanical stops calculates the most appropriate gate leaf...

Страница 10: ...on to stop the learning phase At this point invert the control wires external positions with respect to the terminal on the motor that executed the opening manoeuvre and repeat the self learning proce...

Страница 11: ...button is released LED L7 will start flashing 9 LED L7 flashes position 1 of M1 to command and move motor 1 to position 1 Figure 14 press and hold the f or h button Once the position is reached relea...

Страница 12: ...y whether the leaves can be opened and closed with a force below 390 N 3 lock the motors as described in the respective instruction manual 4 using the control devices transmitter control button key se...

Страница 13: ...2 release the g button when LED L1 starts flashing 3 press the f or h button to move the flashing LED to the LED associated with the function to be modified 4 press the g button to change the status...

Страница 14: ...TABLE PARAMETERS All the Level 2 parameters are factory set as highlighted in GREY in Table 7 and can be modified at any time The parameters can be set to a scale of 1 to 8 The check the value corresp...

Страница 15: ...executed if the sent command remains if the command is interrupted the manoeuvre stops L8 Semi automatic opening hold to run closing L3 Motor speed L1 Very slow Adjusts the motor speed during normal t...

Страница 16: ...roceed with point 2 2 within 3 seconds press the control again and hold it down 3 after roughly 2 seconds the gate will complete the requested manoeuvre in hold to run mode in other words it will cont...

Страница 17: ...stance Verify the cause and increase the motor force if necessary 4 short flashes 1 second pause 4 short flashes Intervention of the STOP input At the start of the manoeuvre or during the movement its...

Страница 18: ...blown verify the cause and replace it with one having the same characteristics Green LED always on Serious anomaly There is a serious problem try disconnecting the power supply to the control unit an...

Страница 19: ...ton to shift flashing of the LED to L8 Anomaly list parameter 4 keep the g button pressed down it must be kept pressed throughout phases 5 and 6 5 wait roughly 3 seconds after which LED L1 correspondi...

Страница 20: ...mation Unlock or only from Oview the following commands Unlock and close and Unlock and open 12 Lock automation Triggers the stoppage of the manoeuvre and locks the automation the control unit will no...

Страница 21: ...CT MAINTENANCE Being an electronic part the control unit does not require any special maintenance Nonetheless the system should be regularly checked to ensure that it works efficiently at least every...

Страница 22: ...us triggers the STOP command SbS input for normally open contacts the closing of the contact triggers the Step by Step command OPEN input for normally open contacts the closing of the contact triggers...

Страница 23: ...ding to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to machinery and amending...

Страница 24: ...24 ENGLISH NOTES...

Страница 25: ...y but contact your trusted installer l Do not modify the system or the programming and adjustment parameters of the control unit your installer is exclusively responsible for these operations Failure...

Страница 26: ...26 ENGLISH NOTES...

Страница 27: ...ENGLISH 27 NOTES...

Страница 28: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0133A01EN_15 01 2019...

Отзывы: