4. Advanced Operation
PROGRAMMABLE AC POWER SOURCE
70
4.1.2 Using RMS Current Limiter
Effective value of output current is limited by the RMS current limiter. While the limiter is working,
icon
is displayed and LIMIT LED illuminates.
Setting values of RMS current limiter are variable, and kept independently for each of 100 V and
200 V ranges.
You can choose whether to make the output off or not upon the triggering of the RMS current
limiter. If you choose to set the output off, specify the continuous operation time of limiter until the
output off becomes effective. Whether output off is set or not and the time setting are common
regardless of the output ranges.
For the default setting range, see
.
--------
Notes
----------------------------------------------------------------------------------------------------------------
It will take time from the limiter starts operation until the output current is restricted enough,
because the RMS current limiter needs to calculate effective value. Use the peak current
limiter to limit the current quickly. For peak current limiter, see
.
RMS current limiter may not be able to limit output current sufficiently if the load impedance
is very small (e.g. output short circuit). Also, RMS current protection may work in this case
and then output is turned off.
When the number of units is increased or decreased based on the power unit energization
setting, the setting is reset to the factory default setting corresponding to the capacity (e.g.
reset to the factory default setting of 4.5 kVA model when only three units of 6 kVA model are
in operation).
In the polyphase model and the polyphase system, the setting of the RMS current limiter is
common to all phases.
If the output off after the continuous operation of the limiter for the specified duration is
enabled, the setting of output-off phase is ignored.
---------------------------------------------------------------------------------------------------------------------------------
Operation procedure
1.
Push [Limiter] soft-key to select 2:Irms Limiter (or push I key). Opens the RMS current limiter
set window.
Содержание DP015S
Страница 1: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL NF Corporation ...
Страница 2: ......
Страница 3: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL DA00027113 001 ...
Страница 4: ......
Страница 18: ......
Страница 19: ...DP Series 1 1 Outline 1 1 Overview 2 1 2 Series Line up and Polyphase System Configuration 2 1 3 Features 4 ...
Страница 24: ...1 Outline PROGRAMMABLE AC POWER SOURCE 6 ...
Страница 215: ...DP Series 197 5 Description of Screen and Menu 5 1 Screen Configuration 198 5 2 Menu Composition 202 ...
Страница 224: ...5 Description of Screen and Menu PROGRAMMABLE AC POWER SOURCE 206 ...
Страница 225: ...DP Series 207 6 Remote Control 6 1 Communication Interface 208 6 2 Remote Local State Switching 214 ...
Страница 237: ...7 8 Replacement Air Filter DP Series 219 フロントグリル フロントグリル Front grill 1 Front grill 2 Figure 7 2 Front Grills ...
Страница 238: ...7 Options PROGRAMMABLE AC POWER SOURCE 220 ...
Страница 239: ...DP Series 221 8 Troubleshooting 8 1 Error Messages and Error Handling 222 8 2 When a Failure is Suspected 229 ...
Страница 298: ......
Страница 300: ......
Страница 302: ......
Страница 303: ......
Страница 304: ...http www nfcorp co jp NF Corporation 6 3 20 Tsunashima Higashi Kohoku ku Yokohama 223 8508 JAPAN ...