d. Replace the cables and any SFP+ or SFP28 transceivers.
e. Power on the controller and monitor the controller LEDs and boot-up codes.
5. Confirm that the appliance Storage Node appears in the Grid Manager and that no alarms appear.
6. From the Grid Manager, select
NODES
, and verify that the BMC IP address for the node controller is
correct.
If the node controller IP address is not valid or is not in the expected range, reconfigure the IP address as
described in the recovery and maintenance instructions.
If you applied additional customization during the original installation, such as setting SNMP
trap destinations or email notifications, you should record and validate the configuration and
reapply it if necessary.
Related information
SG6000-CN: Install into cabinet or rack
View status indicators and buttons on SG6000-CN controller
View boot-up codes for SG6000-CN controller
Replace one or both power supplies in the SG6000-CN controller
The SG6000-CN controller has two power supplies for redundancy. If one of the power
supplies fails, you must replace it as soon as possible to ensure that the compute
controller has redundant power. Both power supplies operating in the controller must be
the same model and wattage.
What you’ll need
• You have determined the physical location in the data center of the controller with the power supply to be
replaced.
Locating the controller in a data center
• If you are replacing only one power supply:
◦
You have unpacked the replacement power supply unit and ensured that it is the same model and
wattage as the power supply unit you are replacing.
◦
You have confirmed that the other power supply is installed and running.
• If you are replacing both power supplies at the same time:
◦
You have unpacked the replacement power supply units and ensured they are the same model and
wattage.
About this task
The figure shows the two power supply units for the SG6000-CN controller, which are accessible from the back
of the controller. Use this procedure to replace one or both of the power supplies. If you are replacing both
power supplies, you must first perform a controlled shut down of the appliance.
146