Comfort Pack Gas CFM and Temperature Rise 43,000 BTU Input
UNIT SIZE
COLOR
SPEED
.1" w.c.
TD
.2" w.c.
TD
.3" w.c.
TD
.4" w.c.
TD
.5" w.c.
TD
CP943043TB
Red
1
1000
37.4
975
38.4
950
39.4
930
40.2
910
41.1
Yellow
2
840
44.6
830
45.1
800
46.8
775
48.3
750
49.9
Blue
3
760
49.2
730
51.3
710
52.7
690
54.2
660
56.7
Black
4
635
58.9
610
61.4
580
64.5
560
66.8
530
70.6
Orange
5
520
72.0
430
87.0
375
99.8
310
120.7
-
n/a
= Factory Heat Speed Setting
Comfort Pack Gas CFM and Temperature Rise 50,000 BTU Input
UNIT SIZE
COLOR
SPEED
.1" w.c.
TD
.2" w.c.
TD
.3" w.c.
TD
.4" w.c.
TD
.5" w.c.
TD
CP943050TB
Red
1
1000
43.1
975
44.2
950
45.3
930
46.3
910
47.3
Yellow
2
840
51.3
830
51.9
800
53.8
775
55.6
750
57.4
Blue
3
760
56.7
730
59.0
710
60.6
690
62.4
660
65.2
Black
4
635
67.8
610
70.6
580
74.2
560
76.9
530
81.2
Orange
5
520
82.8
430
100.1
375
114.8
310
138.9
-
n/a
= Factory Heat Speed Setting
Models
Color
Speed Tap
ESP (in. wc) / CFM
0.1
0.2
0.3
0.4
0.5
CP9430**TB
Red
1
1000
975
950
930
910
Yellow
2
840
830
800
775
750
Blue
3
760
730
710
690
660
Black
4
635
610
580
560
530
Orange
5
520
430
375
310
-
Air Flow Data