Installation Guide
|
Comfort Pack T Series
with up to
95% Gas Heat
34
Check Your Temperature Rise
The temperature rise should be as follows
43MBH = 50°F Nominal (35°F to 65°F)
50MBH = 55°F Nominal (40°F to 70°F)
In order to calculate CFM use the formula
CFM = BTU Output / (1.08 x Temp. Rise)
See page 35 for airflow data.