System Details 65
4.11.8 Main Gas Valve
Part
Check Point
Function
1. To control the amount of gas supplied to the burner based on fan speed.
2. When the unit experiences abnormal combustion, it shuts off the gas valve automatically and prevents
unsafe situations.
Failure Event
Unable to open/close
Effects
1. No flames.
2. No operation of the unit.
Error Code
E003, E012
Diagnostic
1. Visual inspection: Connection and/or breakage of wires.
2. Voltage check: Check range of voltage shown below.
Color/Number
of wires
●
RED-YELLOW: DC 22~24 V
●
WHITE-RED: DC 22~24 V
Test P
out
with
manometer for
specified pressure
range to ensure
that the Gas Valve is
operating properly.