Installation the Outdoor Vent Cover 157
CAUTION
●
Regardless of the vent size listed in the table, the connection to the common vent must always be as large as the largest connector. If the
largest connector and the recommended vent are the same size, use the next largest size for the vent.
●
One short radius elbow = 8 feet, One long radius elbow = 5 feet
Total length (L) = W + H
Required Load
(Total BTU/H)
Model
Total length (ft)
NPE-180A
NPE-180S
NPE-210A
NPE-210S
NPE-240A
NPE-240S
D= 3"
D=4"
D=5"
D=6"
300,000
2
60(18m)
100(30m)
160(48m)
-
330,000
1
1
60(18m)
100(30m)
160(48m)
-
360,000
1
1
60(18m)
100(30m)
160(48m)
-
398,000
2
60(18m)
100(30m)
160(48m)
-
540,000
3
70(21m)
110(33m)
160(48m)
559,000
2
1
70(21m)
110(33m)
160(48m)
578,000
1
2
70(21m)
110(33m)
160(48m)
597,000
3
70(21m)
110(33m)
160(48m)
D=5"
D=6"
D=7"
D=8"
739,000
3
1
80(24m)
120(37m)
-
-
758,000
2
2
80(24m)
120(37m)
-
-
777,000
1
3
80(24m)
120(37m)
-
-
796,000
4
80(24m)
120(37m)
-
-
995,000
5
60(18m)
90(27m)
130(40m)
-
1,194,000
6
-
80(24m)
100(30m)
140(43m)
1,393,000
7
70(21m)
90(27m)
120(36m)
D=7"
D=8"
D=9"
D=10"
1,592,000
8
82(25m)
107(33m)
135(41m)
1,791,000
9
73(22m)
95(29m)
120(37m)
148(45m)
1,990,000
10
65(20m)
85(26m)
108(33m)
133(41m)
2,189,000
11
78(24m)
98(30m)
121(37m)
2,388,000
12
71(22m)
90(27m)
111(34m)
D=9"
D=10"
D=11"
D=12"
2,587,000
13
83(25m)
103(31m)
124(38m)
2,786,000
14
77(23m)
95(29m)
115(35m)
137(42m)
2,985,000
15
72(22m)
89(27m)
108(33m)
128(39m)
3,184,000
16
68(21m)
83(25m)
101(31m)
120(36m)