8.4 Fan Motor Check
1. Turn off outdoor unit and disconnect power supply
2. Disconnect outdoor fan motor power cord from outdoor PCB
3. Measure the resistance value between each windings.
The normal value of different motor show as follows:
Model
YKFG-13-4-38L
YKFG-13-4-38L-4
YKFG-15-4-28-1
YKFG-20-4-10L
YKFG-20-4-5-11
Brand
Welling
Welling
Welling
Welling
Black – Red Main
345
:
75
:
269
:
388
:
Blue – Black AUX
348
:
150
:
224
:
360
:
Model
YKFG-20-4-5-19
YKFG-25-4-6-14
YKFG-28-4-3-7
YKFG-28-4-3-14
YKFG-28-4-6-5
Brand
Welling
Welling
Welling
Welling
Black – Red Main
444
:
287
:
231
:
183.6
:
Blue – Black AUX
470
:
409
:
414
:
206
:
Model
YKFG-45-4-13
YKFG-45-4-22
YKFG-45-4-22-13
YKFG-60-4-2-6
Brand
Dongfang
Welling
Welling
Black – Red Main
125.2
:
168
:
96
:
Blue – Black AUX
83.8
:
141
:
96
:
Service manual
H11 series
e
f
Troubleshooting 48
Содержание MUPR-09-H11-E
Страница 1: ...Service manual MUPR H11 www mundoclima com CL20055 CL20058 R32...
Страница 16: ...Service manual H11 series MUPR 24 H11 I Specifications 7f e...
Страница 17: ...Outdoor unit wiring diagram 16022000019533 Service manual H11 series MUPR 09 12 18 H11 E Specifications 8 f e...
Страница 18: ...Service manual H11 series MUPR 24 H11 E Specifications 9 f e...
Страница 58: ...e Outdoor Unit Disassembly 3 f 1 Panel Plate X101 Service manual H11 series MUPR 09 12 H11 E 2 Dimension...
Страница 59: ...e Outdoor Unit Disassembly 4 f 2 Panel Plate X301 Service manual H11 series MUPR 18 H11 E...
Страница 60: ...e Outdoor Unit Disassembly 5 f 3 Panel Plate X401 Service manual H11 series MUPR 24 H11 E...
Страница 117: ...Service manual H11 series e f Troubleshooting 25...