TS01-IDU: Indoor EEPROM parameter error diagnosis and solution
Description
: Indoor PCB main chip does not receive feedback from EEPROM chip.
Recommended parts to prepare:
• Indoor PCB
Troubleshooting and repair:
Shut off the power supply and
turn it on 2 minutes later.
Is it still displaying
the error code?
YES
Replace the indoor main PCB.
The unit is operating normally.
NO
Remarks:
EEPROM:
A read-only memory whose contents can be erased and reprogrammed using a pulsed voltage.
The location of the EEPROM chip on the indoor PCB is shown in the following image:
Note: This pictures are only for reference, actual appearance may vary.
Service manual
H11 series
7. Troubleshooting by Error Code
Troubleshooting 18