8. Check Procedures
8.1 Temperature Sensor Check
WARNING
Be sure to turn off all power supplies or disconnect all wires to avoid electric shock.
Operate after compressor and coil have returned to normal temperature in case of injury.
1. Disconnect the temperature sensor from PCB (Refer to Chapter 5&6. Indoor&Outdoor Unit Disassembly).
2. Measure the resistance value of the sensor using a multi-meter.
3. Check corresponding temperature sensor resistance value table (Refer to Chapter 8. Appendix).
Note: The picture and the value are only for reference, actual condition and specific value may vary.
.2 Compressor Check
1. Disconnect the compressor power cord from outdoor PCB (Refer to Chapter 6. Outdoor Unit Disassembly)).
2. Measure the resistance value of each winding using a multi-meter.
3. Check the resistance value of each winding in the following table.
Service manual
H11 series
e
f
Troubleshooting 45
Содержание MUPR-09-H11-E
Страница 1: ...Service manual MUPR H11 www mundoclima com CL20055 CL20058 R32...
Страница 16: ...Service manual H11 series MUPR 24 H11 I Specifications 7f e...
Страница 17: ...Outdoor unit wiring diagram 16022000019533 Service manual H11 series MUPR 09 12 18 H11 E Specifications 8 f e...
Страница 18: ...Service manual H11 series MUPR 24 H11 E Specifications 9 f e...
Страница 58: ...e Outdoor Unit Disassembly 3 f 1 Panel Plate X101 Service manual H11 series MUPR 09 12 H11 E 2 Dimension...
Страница 59: ...e Outdoor Unit Disassembly 4 f 2 Panel Plate X301 Service manual H11 series MUPR 18 H11 E...
Страница 60: ...e Outdoor Unit Disassembly 5 f 3 Panel Plate X401 Service manual H11 series MUPR 24 H11 E...
Страница 117: ...Service manual H11 series e f Troubleshooting 25...