3.7 Compressor
WARNING:
Evacuate the system and confirm that there is no refrigerant left in the system before removing the
four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the
system with nitrogen; then repeat the two steps before heating up the brazed parts. The operations above should be
implemented by professionals.)
Note: Remove the panel plate, connection of compressor on PCB (refer to 3.1 Panel plate and 3.2 Electrical
parts) before disassembling sound blanket.
Procedure
Illustration
1) Remove the flange nut of terminal cover
and remove the terminal cover (see CJ_
ODU_COMP_001).
2) Disconnect the connectors (see CJ_ODU_
COMP_002).
CJ_ODU_COMP_001
CJ_ODU_COMP_002
Note: This section is for reference only. Actual unit appearance may vary.
Terminal Cover
Service manual
H11 series
e
Outdoor Unit Disassembly 36
f
Содержание MUPR-09-H11-E
Страница 1: ...Service manual MUPR H11 www mundoclima com CL20055 CL20058 R32...
Страница 16: ...Service manual H11 series MUPR 24 H11 I Specifications 7f e...
Страница 17: ...Outdoor unit wiring diagram 16022000019533 Service manual H11 series MUPR 09 12 18 H11 E Specifications 8 f e...
Страница 18: ...Service manual H11 series MUPR 24 H11 E Specifications 9 f e...
Страница 58: ...e Outdoor Unit Disassembly 3 f 1 Panel Plate X101 Service manual H11 series MUPR 09 12 H11 E 2 Dimension...
Страница 59: ...e Outdoor Unit Disassembly 4 f 2 Panel Plate X301 Service manual H11 series MUPR 18 H11 E...
Страница 60: ...e Outdoor Unit Disassembly 5 f 3 Panel Plate X401 Service manual H11 series MUPR 24 H11 E...
Страница 117: ...Service manual H11 series e f Troubleshooting 25...