TS12-S: Inverter compressor drive error diagnosis and solution
Description:
An abnormal inverter compressor drive is detected by a special detection circuit, including communication
signal detection, voltage detection, compressor rotation speed signal detection and so on.
Recommended parts to prepare:
• Connection wires
• IPM module board
• Outdoor fan assembly
• Compressor
• Outdoor PCB
Troubleshooting and repair:
Check the wiring between the
PCB and compressor.
Is it improperly wired?
Ensure proper connections or replace
the wires and connectors.
YES
Check the IPM.
NO
Is it functioning
properly?
Replace the IPM board or
replace the outdoor PCB.
NO
Check the outdoor fan and
the outdoor unit ventilation.
YES
Is it functioning
properly?
Please refer to “Fan
Speed Malfunction”
NO
Check the compressor
resistance values.
YES
Are they within
acceptable parameters?
Replace the compressor.
NO
Replace the outdoor PCB.
YES
Note: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.
Service manual
H11 series
e
f
Troubleshooting 40
Содержание MUPR-09-H11-E
Страница 1: ...Service manual MUPR H11 www mundoclima com CL20055 CL20058 R32...
Страница 16: ...Service manual H11 series MUPR 24 H11 I Specifications 7f e...
Страница 17: ...Outdoor unit wiring diagram 16022000019533 Service manual H11 series MUPR 09 12 18 H11 E Specifications 8 f e...
Страница 18: ...Service manual H11 series MUPR 24 H11 E Specifications 9 f e...
Страница 58: ...e Outdoor Unit Disassembly 3 f 1 Panel Plate X101 Service manual H11 series MUPR 09 12 H11 E 2 Dimension...
Страница 59: ...e Outdoor Unit Disassembly 4 f 2 Panel Plate X301 Service manual H11 series MUPR 18 H11 E...
Страница 60: ...e Outdoor Unit Disassembly 5 f 3 Panel Plate X401 Service manual H11 series MUPR 24 H11 E...
Страница 117: ...Service manual H11 series e f Troubleshooting 25...