Two or more detectors and a call-point must be grouped( by zone), when one detector
detects an alarm condition the panel treats that alarm condition as a normal alarm
condition the alarm relay will change state, the alarm led will activate, nac will activate
(silenceable).
When the second detector detects an alarm condition the common alarm nac will
activate (silenceable), output of
FSUOM-G
will activate after 30
seconds and will
deactivate after 12 seconds.
When operating the call-point at any-time will activate the solenoid
A example of GAS release screen
3.4 Remote Annunciator
The remote Annunciator device developed in order to give allowance users supervision
and control on the MA-1000 fire system from remote places. The unit connected by
RS485 communication port to the MA-1000. You can connect up to 8 units on this port.
The unit has 4 lines display similar to the MA-1000 display and show the same
messages.
Содержание MA-1000
Страница 2: ...1 ...
Страница 3: ...2 ...
Страница 15: ...14 MA 1000 ...
Страница 17: ...16 Peripheral Devices ...
Страница 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Страница 63: ...62 ...
Страница 71: ...70 ...
Страница 76: ...75 FIGURE 12 Allocated devices list ...
Страница 80: ...79 FIGURE 14 Allocated List ...
Страница 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Страница 88: ...87 Save as TXT format ...
Страница 89: ...88 Panel outputs Save as EXEL format ...
Страница 90: ...89 2 2 13 History Events 1 Select Read History button FIGURE 23 Read History FIGURE 23 Save Event list ...
Страница 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Страница 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Страница 98: ...97 ...
Страница 103: ...102 Fig 1 ...
Страница 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Страница 106: ...105 ...
Страница 107: ...107 ...