11
2 Installations
Essential please read before proceeding!
The equipment described in this manual is listed by ETL TESTING LABORATORIES, for use in fire
alarm signaling systems, only when installed in accordance with this manual and the latest National
Fire Protection Association Standards NFPA 72; the National Electrical Code (NFPA 70); the Life
Safety Code (NFPA 101); and/or the local authority having jurisdiction (AHJ).
It is possible to apply system components incorrectly or arrange system components and installation
wiring so that required life safety functions are NOT performed. As a result, lives may be lost.
To minimize this possibility:
DO NOT deviate from any installation instructions contained in this manual.
DO NOT assume any installation details not shown in this manual.
DO NOT alter any mechanical or electrical features of the equipment supplied
BE FAMILIAR with the building code, fire prevention code, and/or requirements of the Authority
Having Jurisdiction (AHJ) in the locale of the installation.
!Caution!
Under normal and fault conditions, AC line voltages may be present on any terminal. Touching any
component could be hazardous and result in loss of life. A short circuit can result in arcing that could
cause molten metal injuries to testing personal.
To minimize this possibility, only qualified electrical technicians familiar with electrical hazards
should perform these checkout procedures. Safety glasses should be worn by such personnel, and
instruments used for voltage measurement should be designed for the purpose and should be in
good mechanical and working order.
If there is application or installation information that is not clear or not covered in this manual, please
contact us at: MTECH Technical Support at +972-4-6000610
or by email:
2.1
Agency Requirements
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
The PANEL is listed by ETL TESTING LABORATORIES to UL 864 9
th
edition as a FACP control
unit for use in NFPA 72 systems.
Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the
specific section of the manual for additional requirements.
All field wiring must be installed in accordance with NFPA 70 National Electric Code.
Use UL listed smoke detectors and notification appliances compatible with the PANEL
Содержание MA-1000
Страница 2: ...1 ...
Страница 3: ...2 ...
Страница 15: ...14 MA 1000 ...
Страница 17: ...16 Peripheral Devices ...
Страница 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Страница 63: ...62 ...
Страница 71: ...70 ...
Страница 76: ...75 FIGURE 12 Allocated devices list ...
Страница 80: ...79 FIGURE 14 Allocated List ...
Страница 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Страница 88: ...87 Save as TXT format ...
Страница 89: ...88 Panel outputs Save as EXEL format ...
Страница 90: ...89 2 2 13 History Events 1 Select Read History button FIGURE 23 Read History FIGURE 23 Save Event list ...
Страница 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Страница 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Страница 98: ...97 ...
Страница 103: ...102 Fig 1 ...
Страница 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Страница 106: ...105 ...
Страница 107: ...107 ...